<ESpecicationsCommontoFieldMateBasicandAdvance>
E-42
IM 01R01A01-01E 9th Edition : May 31, 2013-00
FOUNDATIONeldbusH1DevicesBlocks
In Parameter Manager, only the TB (transducer block) and resource block are selected to be
displayed/setbydefaultforFOUNDATIONeldbusH1devices.Blocksotherthanthesecanbe
addedintheoptionsettings.Thesesettingsbecomecommondenitionsfordevicesofthesame
type (model).
Morespecically,theread/writepermissioncanbesetforallblocksinadevice.However,only
the write permission is enabled/disabled for the transducer block and resource block. The read
permission is always enabled.
MIBParametersandBlockTagHeadersofFOUNDATIONeldbusH1
Devices
This function does not support the MIB parameters (NMIB and SMIB parameters) and block
headers(functionblocktags,etc.)ofFOUNDATIONeldbusH1devices.
FOUNDATIONeldbusH1DeviceMode
WhendownloadingtoanFOUNDATIONeldbusdevice,thedefaultprocessistoautomatically
enter O/S (Out of Service) mode and then switch back to the previous mode after writing
completes. This process can be enabled or disabled with the “Change O/S Mode during
download” setting in the Option settings.
Categorize Parameters by Class Attribute
Thisfunctionallowstheusertocategorizeanddisplaydeviceparametersbyclassattribute.
This function is applied to all currently displayed blocks and allows the user to display
parameters that have a class attribute in the order of the blocks.
• Thefollowing5tabsaredisplayedforFOUNDATIONeldbusH1devices.
Alarm, Tune, Operate, Service, Diagnostic
• Thefollowing4tabsaredisplayedforHARTdevices.
UPLOAD,MENU,Service,Diagnostic
Custom Tab
TheCustomtaballowstheusertofreelyassign,acrossFOUNDATIONeldbusH1blocks,alist
of parameters that needs to be monitored on a device type basis.
To add and display items in the Custom tab, select the desired parameters in a window other
than the Custom tab and then select “Send to Custom tab.” To remove parameters from the
Custom tab, select a parameter and click “Delete from Custom tab” on the Custom tab.