<F Advance>
F-63
IM 01R01A01-01E 9th Edition : May 31, 2013-00
PROFIBUS Devices
WhenyouuseaPROFIusbofSofting,asaPROFIBUSDPcommunicationcard,theBuilt-in
ConnectionmodeisavailableforcommunicationwithPROFIBUSdevices.
TheSegmentViewerdisplaysthePROFIBUSdevices.
ThelistofdevicesinthePROFIBUSDPnetwork() is displayed.
: Upto127devices(subjecttothePROFIBUSspecication).
DevicestobedisplayedareonlyPROFIBUSdevicesinthePROFIBUSDPnetworktowhichthe
PROFIusb is connected. Accordingly, the devices listed below are not displayed. For the devices
listed below, you can access them by creating a network topology in DTM Works using the
COMM/Gateway DTM (FDT Project).
DevicesunavailableinSegmentViewerBICmodewindow(PROFIBUS)
- DevicesconnectedtothePROFIBUSDPnetworkusingacommunicationcardotherthan
the PROFIusb.
- PA devices connected with a Siemens DP/PA link.
- HARTdevicesviaPROFIBUS/HARTgateway.
The following shows the display items.
Items: Address, IDENT number, Vendor, Model (Device Type), Device ID
F050104E.ai
IDENT number: 0x070d
Vendor: YOKOGAWA
Model: EJA
(
0x070d)
Device ID: PB37070DJ0000902
34
The device tag
is displayed.
PT101
The status display icon is
always white. When you click it,
nothing displays.
Click this to execute Device
Setup and start up DTM Works.
Displays a red “!” icon for a
device not registered in the
database.
Yellow icon is displayed
when difference of device
information is found.
Displays icons indicating a
device flag and memo flag
for a device registered in the
database.
Displays the device address.
Figure F-5-5 Display of PROFIBUS Device in Segment Viewer
For address setting, refer to Part E3-2, explanation of Setting Device Station Address for
PROFIBUSDevices.