User’sManualFVX110Fieldbus Segment IndicatorIM 01S01C01-01ENIM 01S01C01-01EN2nd Edition
<1. Introduction>1-3IM 01S01C01-01EN1.3 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<Appendix 2. Integrator (IT) Block>A2-4IM 01S01C01-01ENA2.3.2 AdditionThe following three options are available for addition:• TOTAL: Add
<Appendix 2. Integrator (IT) Block>A2-5IM 01S01C01-01ENTable A2.1 INTEG_TYPENameIntegration MethodIntegration RangeReset Trigger (Reset if
<Appendix 2. Integrator (IT) Block>A2-6IM 01S01C01-01ENOUT.Value, OUT_TRIP.Status, and OUT_PTRIP.Status are determined by the ratio of the
<Appendix 2. Integrator (IT) Block>A2-7IM 01S01C01-01ENFor counting up, the OUT value is as follows:● OUT < TOTAL_SP - PRE_TRIP OUT_TR
<Appendix 2. Integrator (IT) Block>A2-8IM 01S01C01-01ENWhen OP_CMD_INT has become "H" and a reset was made, OP_CMD_INT automatica
<Appendix 2. Integrator (IT) Block>A2-9IM 01S01C01-01EN4.) Judging OUT_TRIP and OUT_PTRIP (see A2.5)OUT_TRIP and OUT_PTRIP are judged agai
<Appendix 2. Integrator (IT) Block>A2-10IM 01S01C01-01ENIndexParameter NameInitial ValueWrite ModeViewDenition1 2 3 426 SRTOTAL 0.0 4 Indi
<Appendix 2. Integrator (IT) Block>A2-11IM 01S01C01-01ENIndexParameter NameInitial ValueWrite ModeViewDenition1 2 3 439 UPDATE_EVT Indicat
<Appendix 3. Input Selector (IS) Block>A3-1IM 01S01C01-01ENAppendix 3. Input Selector (IS) BlockThe function of the Input Selector (IS) bl
<Appendix 3. Input Selector (IS) Block>A3-2IM 01S01C01-01ENOutput Parameters (Computation or Selection Results) OUT : Block output SELECTE
<2. Handling Cautions>2-1IM 01S01C01-01EN2. Handling CautionsThis chapter provides important information on how to handle the indicator. R
<Appendix 3. Input Selector (IS) Block>A3-3IM 01S01C01-01ENA3.2 Input Section A3.2.1 Mode Handling The Input Selector block’s operations
<Appendix 3. Input Selector (IS) Block>A3-4IM 01S01C01-01ENA3.2.2 MIN_GOOD Handling If there is no selectable input or if the number of se
<Appendix 3. Input Selector (IS) Block>A3-5IM 01S01C01-01EN A3.3 Selection The following processing is performed after completing input pr
<Appendix 3. Input Selector (IS) Block>A3-6IM 01S01C01-01ENA3.3.2 SELECTION Handling If the value of OP_SELECT is “0,” input selection usi
<Appendix 3. Input Selector (IS) Block>A3-7IM 01S01C01-01ENWhen SELECT TYPE is “Minimum” The IS block selects the input with the minimum va
<Appendix 3. Input Selector (IS) Block>A3-8IM 01S01C01-01ENWhen SELECT TYPE is “Maximum” The IS block selects the input with the maximum va
<Appendix 3. Input Selector (IS) Block>A3-9IM 01S01C01-01ENWhen SELECT TYPE is “Middle” If there is more than one valid input and the numbe
<Appendix 3. Input Selector (IS) Block>A3-10IM 01S01C01-01ENIf there is an odd number of valid inputs: IN_1 = 23SELECT_TYPE = MiddleSTATUS_
<Appendix 3. Input Selector (IS) Block>A3-11IM 01S01C01-01ENWhen SELECT TYPE is “Average” The block calculates the average of the valid inp
<Appendix 3. Input Selector (IS) Block>A3-12IM 01S01C01-01ENA3.4 Output Processing A3.4.1 Handling of SELECTED For the value output to SE
<2. Handling Cautions>2-2IM 01S01C01-01EN(c) Shock and VibrationAlthough the indicator is designed to be relatively resistant to shock and
<Appendix 3. Input Selector (IS) Block>A3-13IM 01S01C01-01ENA3.4.2 OUT Processing OUT is an output parameter used to send the value select
<Appendix 3. Input Selector (IS) Block>A3-14IM 01S01C01-01ENA3.4.3 STATUS_OPTS Bit DescriptionUse Uncertain as Good Causes all inputs (OP_
<Appendix 3. Input Selector (IS) Block>A3-15IM 01S01C01-01ENRelative IndexIndex IS1Index IS2ParameterWrite ModeValid RangeInitial ValueView
<Appendix 3. Input Selector (IS) Block>A3-16IM 01S01C01-01ENA3.6 Application Example The following describes the temperature control syste
<Appendix 4. Arithmetic (AR) Block>A4-1IM 01S01C01-01ENAppendix 4. Arithmetic (AR) Block The Arithmetic (AR) block switches two main input
<Appendix 4. Arithmetic (AR) Block>A4-2IM 01S01C01-01ENA4.2 Input Section There are ve inputs: IN and IN_LO main inputs and IN_1, IN_2, a
<Appendix 4. Arithmetic (AR) Block>A4-3IM 01S01C01-01ENA4.2.3 INPUT_OPTS INPUT_OPTS has an option that handles an input with “uncertain” o
<Appendix4.Arithmetic(AR)Block>A4-4IM 01S01C01-01ENA4.3 ComputationSectionA4.3.1 ComputingEquationsThis subsection shows computin
<Appendix 4. Arithmetic (AR) Block>A4-5IM 01S01C01-01ENA4.4.1 Mode Handling Mode OutputAuto OUT = PRE_OUTMAN For OUT, the OUT value in the
<Appendix 4. Arithmetic (AR) Block>A4-6IM 01S01C01-01ENA4.5 List of the Arithmetic Block ParametersRelativeIndexIndexAR1IndexAR2ParameterW
<2. Handling Cautions>2-3IM 01S01C01-01EN2.8 Installation of an Explosion-Protected InstrumentIf a customer makes a repair or modication
<Appendix 4. Arithmetic (AR) Block>A4-7IM 01S01C01-01ENRelativeIndexIndexAR1IndexAR2ParameterWrite ModeValid RangeInitial ValueViewDescript
<Appendix 4. Arithmetic (AR) Block>A4-8IM 01S01C01-01ENRelativeIndexIndexAR1IndexAR2ParameterWrite ModeValid RangeInitial ValueViewDescript
<Appendix 5. PID Block>A5-1IM 01S01C01-01ENAppendix 5. PID BlockA PID block performs the PID control computation based on the deviation of
<Appendix 5. PID Block>A5-2IM 01S01C01-01ENA5.3 Parameters of PID BlockNOTE: In the table below, the Write column shows the modes in which
<Appendix 5. PID Block>A5-3IM 01S01C01-01ENIndexIndexPID1IndexPID2ParameterNameDefault(factory setting)Write Valid Range Description22 8022
<Appendix 5. PID Block>A5-4IM 01S01C01-01ENIndexIndexPID1IndexPID2ParameterNameDefault(factory setting)Write Valid Range Description45 8045
<Appendix 5. PID Block>A5-5IM 01S01C01-01ENA5.4 PID Computation DetailsA5.4.1 PV-proportional and -derivative Type PID (I-PD) Control Al
<Appendix 5. PID Block>A5-6IM 01S01C01-01ENA5.7 Control Action BypassThe PID control computation can be bypassed so as to set the SP value
<Appendix 5. PID Block>A5-7IM 01S01C01-01ENTransitionDestinationModeConditionNOTConditionsRCas* ** 7. If RCas is set in MODE_BLK.target - A
<Appendix 5. PID Block>A5-8IM 01S01C01-01ENA5.12 External-output TrackingExternal tracking is an action of outputting the value of the rem
<2. Handling Cautions>2-4IM 01S01C01-01ENb. FM Intrinsically safe and Nonincendive TypeFVX110 Fieldbus Segment Indicator with optional cod
<Appendix 5. PID Block>A5-9IM 01S01C01-01ENA5.15 Manual FallbackManual fallback denotes an action in which a PID block changes mode to Man
<Appendix 5. PID Block>A5-10IM 01S01C01-01ENNOTE: If a control block is connected as a cascade primary block of the PID block in question,
<Appendix 5. PID Block>A5-11IM 01S01C01-01ENA5.20 View Object for PID Function BlockRelative IndexParameter MnemonicVIEW 1VIEW 2VIEW 3VIEW
<Appendix 6. Multiple Analog Output (MAO) Block>A6-1IM 01S01C01-01ENAppendix 6. Multiple Analog Output (MAO) Block The MAO function block
<Appendix 6. Multiple Analog Output (MAO) Block>A6-2IM 01S01C01-01ENOther parametersFSTATE_VAL1Value transferred as input 1 to LCD Transduc
<Appendix 6. Multiple Analog Output (MAO) Block>A6-3IM 01S01C01-01ENA6.3 Fault StateBlocks and inputs in the MAO function block that are
<Appendix 6. Multiple Analog Output (MAO) Block>A6-4IM 01S01C01-01ENA6.4 Status TransitionsNote that inputs IN_1 – IN_8 status are not tr
<Appendix 6. Multiple Analog Output (MAO) Block>A6-5IM 01S01C01-01ENRelative IndexParameterWrite ModeValid RangeInitial ValueViewDescriptio
<Appendix 7. Link Master Functions>A7-1IM 01S01C01-01ENAppendix 7. Link Master FunctionsA7.1 Link Active SchedulerA link active scheduler
<Appendix 7. Link Master Functions>A7-2IM 01S01C01-01ENA7.3 Transfer of LASThere are two procedures for an LM to become the LAS: • If the
<2. Handling Cautions>2-5IM 01S01C01-01EN Note: In the rating 1, the output current of the barrier must be limited by a resistor “Ra” such
<Appendix 7. Link Master Functions>A7-3IM 01S01C01-01EN(2) In the LAS settings of the FVX110, set the values of V(ST), V(MRD), and V(MID)
<Appendix 7. Link Master Functions>A7-4IM 01S01C01-01ENA7.5 LM ParametersA7.5.1 LM Parameter ListThe tables below show LM parameters. Me
<Appendix 7. Link Master Functions>A7-5IM 01S01C01-01ENIndex(SM)Parameter NameSub-parameter Name(Sub Index)Default FactorySettingAccess Rem
<Appendix 7. Link Master Functions>A7-6IM 01S01C01-01ENA7.5.2 Descriptions for LM ParametersThe following describes LM parameters of an FV
<Appendix 7. Link Master Functions>A7-7IM 01S01C01-01EN(7) CurrentLinkSettingRecord and ConguredLinkSettingsRecordCurrentLinkSettingRecor
<Appendix 7. Link Master Functions>A7-8IM 01S01C01-01EN(12) LinkScheduleActivationVariableWriting the version number of an LAS schedule, wh
<Appendix 7. Link Master Functions>A7-9IM 01S01C01-01ENQ3. On a segment where an FVX110 works as the LAS, another device cannot be connect
<Appendix 8. Software Download>A8-1IM 01S01C01-01ENAppendix 8. Software DownloadA8.1 Benets of Software DownloadThis function enables yo
<Appendix 8. Software Download>A8-2IM 01S01C01-01ENA8.4 Software Download SequenceThe owchart below outlines the software download proced
<Appendix 8. Software Download>A8-3IM 01S01C01-01ENA8.6 Steps after Activating a Field DeviceWhen the communication with a eld device has
<2. Handling Cautions>2-6IM 01S01C01-01EN● Installation Diagram for Nonincendive (Division 2 Installation)Non-Hazardous LocationFM Approv
<Appendix 8. Software Download>A8-4IM 01S01C01-01ENA8.8 Resource Block’s Parameters Relating to Software DownloadTable A8.3 Additional Pa
<Appendix 8. Software Download>A8-5IM 01S01C01-01ENA8.9 System/Network Management VFD Parameters Relating to Software DownloadTable A8.5
<Appendix 8. Software Download>A8-6IM 01S01C01-01ENA8.10 Comments on System/Network Management VFD Parameters Relating to Software Downloa
<Appendix 8. Software Download>A8-7IM 01S01C01-01EN(3) DOMAIN_HEADERSub IndexElementSize (Bytes)Description1 Header Version Number 2 Indic
iIM 01S01C01-01ENRevision Information Title : FVX110 Fieldbus Segment Indicator Manual No. : IM 01S01C01-01ENEdition Date Page Revised Item1st N
<2. Handling Cautions>2-7IM 01S01C01-01ENCableThe cable used to interconnect the devices needs to comply with the following parameters:Loop
<2. Handling Cautions>2-8IM 01S01C01-01ENNon-hazardous Location Equipment32 V DC Max. 15 mA DC SignalNon-Hazardous LocationsHazardous Locat
<2. Handling Cautions>2-9IM 01S01C01-01ENElectrical Data:• Rating 1 (Entity) For Groups A, B, C, D, E, F, and G or Group IIC Ui (vmax) =
iIM 01S01C01-01ENFVX110Fieldbus Segment IndicatorIM 01S01C01-01EN 2nd Edition2nd Edition: July 2011(YK)All Rights Reserved, Copyright © 2010, Yokogaw
<2. Handling Cautions>2-10IM 01S01C01-01EN2.8.3 CENELEC ATEX Certication(1) Technical Dataa. CENELEC ATEX (DEKRA) Intrinsically Safe Ty
<2. Handling Cautions>2-11IM 01S01C01-01ENThe criterion for such interconnection is that the voltage (Ui), the current (Ii) and the power (
<2. Handling Cautions>2-12IM 01S01C01-01ENNote 2. Electrical Data• Supply voltage: 32 V dc max.Output current: 15 mA dcNote 3. Installat
<2. Handling Cautions>2-13IM 01S01C01-01EN(6) Name PlateMODELSUFFIXSUPPLYOUTPUTSTYLENO.F0213.ai● Name plate● Tag plate for flameproof type
<2. Handling Cautions>2-14IM 01S01C01-01ENb. IECEx Intrinsically Safe TypeCaution for IECEx Intrinsically safe type.Note 1. FVX110 Fieldb
<3. Component Names>3-1IM 01S01C01-01EN3. Component NamesF0301.aiTerminal box coverConduit connection(Note 1)Conduit connectionScroll Knob
<4. About Fieldbus>4-1IM 01S01C01-01EN4. About Fieldbus4.1 OutlineFieldbus is a widely used bi-directional digital communication protocol
<4. About Fieldbus>4-2IM 01S01C01-01EN4.3 Logical Structure of Each BlockF0401.aiFVX110System/network management VFDLink MasterPD TagResou
<5. Installation>5-1IM 01S01C01-01EN5. Installation5.1 Precautions Before installing the indicator, read the cautionary notes in section
<5. Installation>5-2IM 01S01C01-01EN5.3 Wiring5.3.1 Wiring PrecautionsIMPORTANT• Lay wiring as far as possible from electrical noise sou
iiIM 01S01C01-01EN5.5 Connection of Devices ...5-35.6 Host Setting
<5. Installation>5-3IM 01S01C01-01EN Flameproof metal conduit wiring• A seal tting must be installed near the terminal box connection p
<5. Installation>5-4IM 01S01C01-01ENField deviceFieldbus power supplyTerminatorTerminatorFVX110HOSTF0506.aiFigure 5.6 CablingSUPPLY +–Powe
<5. Installation>5-5IM 01S01C01-01ENNot used0x000xF70xF80x0F0x100x130x140xFB0xFC0xFFV(FUN)V(FUN)+V(NUN)LM deviceBridge deviceUnused V(NUN)B
<5. Installation>5-6IM 01S01C01-01EN5.8 Integration of DDIf the host supports DD (Device Description), the DD of the FVX110 needs to be in
<6. Conguration>6-1IM 01S01C01-01EN6. CongurationThis chapter describes how to adapt the function and performance of the FVX110 to suit
<6. Conguration>6-2IM 01S01C01-01EN6.2 Network DenitionBefore connection of devices with Fieldbus, dene the Fieldbus network. Allocate
<6. Conguration>6-3IM 01S01C01-01EN6.3 Denition of Combining Function BlocksThe input/output parameters for function blocks are combined
<6. Conguration>6-4IM 01S01C01-01EN6.4 Setting of Tags and AddressesThis section describes the steps in the procedure to set PD Tags and
<6. Conguration>6-5IM 01S01C01-01ENTable 6.4 VCR Static EntrySub-indexParameter Description1 FasArTypeAndRole Indicates the type and role
<6. Conguration>6-6IM 01S01C01-01ENTable 6.5 VCR ListIndex(SM)VCRNumberFactory Setting303 1 For system management (Fixed)304 2 Server (Lo
iiiIM 01S01C01-01EN9.2.3 Standard categories for NAMUR NE-107 instrument diagnostics alarms ...
<6. Conguration>6-7IM 01S01C01-01EN6.6.2 Trend ObjectIt is possible to set the parameter so that the function block automatically transmi
<6. Conguration>6-8IM 01S01C01-01ENTable 6.10 View Object for Resource BlockRelativeIndexParameter MnemonicView1 23_1 3_2 4_1 4_21 ST_REV
<6. Conguration>6-9IM 01S01C01-01ENTable 6.11 View Object for LCD Transducer BlockRelativeIndexParameter MnemonicView1 2 3 41ST_REV2 2 2
<6. Conguration>6-10IM 01S01C01-01ENTable 6.12 Indexes of View for Each BlockVIEW1VIEW2VIEW3VIEW4Resourse Block 40100 40101 40102 40103LC
<7. Explanation of Basic Items>7-1IM 01S01C01-01EN7. Explanation of Basic Items7.1 OutlineThis chapter provides an outline of the LCD t
<7. Explanation of Basic Items>7-2IM 01S01C01-01ENTable 7.1 Indicated valuesComponent nameDescriptionTop eld Shows the Main Tag and page
<7. Explanation of Basic Items>7-3IM 01S01C01-01ENTable 7.2 Communication status indicationsQuality Sub-statuslimit (Upper line: LCD indi
<7. Explanation of Basic Items>7-4IM 01S01C01-01EN7.3.5 Indicator settingsTo use the FVX110 as a eld indicator, information (Main Tag an
<7. Explanation of Basic Items>7-5IM 01S01C01-01ENNOTE• When 5 digits are displayed, the values beyond the decimal point are rounded off.
<7. Explanation of Basic Items>7-6IM 01S01C01-01ENNOTEDISP_PAGE_INFO does not display numbers of function blocks whose inputs are valid. It
ivIM 01S01C01-01ENA2.3 Adder ... A2-3A2.3
<7. Explanation of Basic Items>7-7IM 01S01C01-01EN7.3.6 Other display settingsSetting display mode after backlight off (DISP_QUIET_MODE)T
<7. Explanation of Basic Items>7-8IM 01S01C01-01EN7.3.7 Flow chart of indicator settingsSetting block that is the source of input indicat
<7. Explanation of Basic Items>7-9IM 01S01C01-01EN7.3.8 Units the auto link function allows you to display on the LCDIndex Unit Display o
<7. Explanation of Basic Items>7-10IM 01S01C01-01ENIndex Unit Display on the LCD1070 ft/minf t/ m i n1071 yd/miny d/ m i n1072 in/hi n / h1
<7. Explanation of Basic Items>7-11IM 01S01C01-01ENIndex Unit Display on the LCD1142 psiap s i a1143 psigp s i g1144 g/cm2g/ c m21145 k/cm2
<7. Explanation of Basic Items>7-12IM 01S01C01-01ENIndex Unit Display on the LCD1214 pAp A1215 CC1216 MCM C1217 kCk C1218 μCu C1219 nCn C12
<7. Explanation of Basic Items>7-13IM 01S01C01-01ENIndex Unit Display on the LCD1286 μΩu o h m1287 SS1288 kSk S1289 mSm S1290 μSu S1291 Ω•m
<7. Explanation of Basic Items>7-14IM 01S01C01-01ENIndex Unit Display on the LCD1358 CFHC F H1359 ft3/df t3/ d1360 CFM (0°C, 1atm)C F M( S
<7. Explanation of Basic Items>7-15IM 01S01C01-01ENIndex Unit Display on the LCD1430 lb/Igall b /I G a l1431 kcal/sk c a l/ s1432 kcal/mink
<7. Explanation of Basic Items>7-16IM 01S01C01-01ENIndex Unit Display on the LCD1502 Mm3/minM m3/ m i n1503 μm3/hu m3/ h1504 mm3/hm m3/ h15
vIM 01S01C01-01ENAppendix 5. PID Block ...A5-1A5.1 Function Diagram
<7. Explanation of Basic Items>7-17IM 01S01C01-01ENIndex Unit Display on the LCD1574 ftH2Og (4°C)f t H 2 Og ( 4 C )1575 ftH2Oa (68°F)f t H
<7. Explanation of Basic Items>7-18IM 01S01C01-01ENIndex Unit Display on the LCD1646 mBaram B a ra1647 1/32 mec1 / 3 2m s1648 kgalk g a l16
<8. Explanation of Basic Items (switching displays)>8-1IM 01S01C01-01EN8. Explanation of Basic Items (switching displays)Turn the scroll k
<8. Explanation of Basic Items (switching displays)>8-2IM 01S01C01-01EN8.2 Continuous Scroll Mode (scan mode)To scroll display continuosl
<9. In-Process Operation>9-1IM 01S01C01-01EN9. In-Process OperationThis chapter describes the procedure performed when changing the operat
<9. In-Process Operation>9-2IM 01S01C01-01ENAn alert has following structure:Table 9.1 Alert ObjectSubindexParameter NameExplanationAnalog
<9. In-Process Operation>9-3IM 01S01C01-01ENTable 9.2 Field Diagnostic AlertIndication of FD_*_ACTIVE Indication of FD_RECOMMEN_ACT Soluti
<9. In-Process Operation>9-4IM 01S01C01-01EN9.3 Device Diagnostic Simulation FunctionIt is possible to conduct testing for the downstream
<9. In-Process Operation>9-5IM 01S01C01-01EN9.4 Write lock (Write-protect) functionThe FVX110 is provided with a write lock (write-protec
<10. Maintenance>10-1IM 01S01C01-01EN10. Maintenance10.1 OverviewMaintenance of the indicator is easy due to its modular construction. T
viIM 01S01C01-01ENA7.2 Link Master ... A7-1A7.3 Tr
<10. Maintenance>10-2IM 01S01C01-01ENNOTELong continuous use during high or low temperatures may reduce visibility. Should this happen, rep
<11. Device Information>11-1IM 01S01C01-01EN11. Device Information11.1 DEVICE STATUSDevice status for the FVX110 are indicated by using p
<11. Device Information>11-2IM 01S01C01-01ENTable 11.2 Contents of DEVICE_STATUS_2 (index 1046)Hexadecimal Diplay through DD DescriptionNA
<11. Device Information>11-3IM 01S01C01-01EN11.2 Status of Each Parameter in Failure ModeFollowing tables summarize the value of FVX110 pa
<12. Parameter Lists>12-1IM 01S01C01-01EN12. Parameter ListsNote: The Write Mode column contains the modes in which each parameter is wr
<12. Parameter Lists>12-2IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 20 1020 CYCLE_SEL Sc
<12. Parameter Lists>12-3IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 54 1054 SOFTDWN_FORMA
<12. Parameter Lists>12-4IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 86 1086 FD_CHECK_PRI
<12. Parameter Lists>12-5IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 5 2005 MODE_BLK AUTO
<12. Parameter Lists>12-6IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 25 2025 DISP_PAGE_INF
<1. Introduction>1-1IM 01S01C01-01EN1. IntroductionThank you for purchasing the FVX110 Fieldbus Segment Indicator.Your FVX110 Fieldbus Seg
<12. Parameter Lists>12-7IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 42 2042 IN09_CONNECTI
<12. Parameter Lists>12-8IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 65 2065 IN_16 Status:
<12. Parameter Lists>12-9IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 81 2081 IN06_MAIN_TAG
<12. Parameter Lists>12-10IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 97 2097 IN11_SUB_TAG
<12. Parameter Lists>12-11IM 01S01C01-01ENRelative Index Index Parameter Name Factory Default Write Mode Explanation 112 2112 IN16_SUB_TA
<13. General Specications>13-1IM 01S01C01-01EN13. General Specications13.1 Functional SpecicationsFunctional specications for Fieldbu
<13. General Specications>13-2IM 01S01C01-01EN13.2 Physical SpecicationsEnclosureMaterialHousing: Low copper cast aluminum alloy with po
<13. General Specications>13-3IM 01S01C01-01EN13.4 Optional Specications (For Explosion Protected type)Item Description CodeFactory Mutu
<13. General Specications>13-4IM 01S01C01-01ENItem Description CodeIECExScheme IECEx Flameproof Approval *1Applicable Standard: IEC 60079-
<13. General Specications>13-5IM 01S01C01-01EN13.6 DimensionsElectrical connection for code 5, 9, A and D54(2.13)6(0.24)12(0.47)2-inch pi
<1. Introduction>1-2IM 01S01C01-01EN(a) Installation• This instrument may only be installed by an engineer or technician who has an exper
<Appendix 1. Signal Characterizer (SC) Block>A1-1IM 01S01C01-01ENAppendix 1. Signal Characterizer (SC) BlockThe Signal Characterizer (SC)
<Appendix 1. Signal Characterizer (SC) Block>A1-2IM 01S01C01-01ENYorXX or Y Input sectionLine-segment factordetermination sectionOutput sec
<Appendix 1. Signal Characterizer (SC) Block>A1-3IM 01S01C01-01ENA1.3 Line-segment Factor Determination SectionWhen the mode is AUTO and n
<Appendix 1. Signal Characterizer (SC) Block>A1-4IM 01S01C01-01ENExample of the case where SWAP_2 is on (monotone increase):The input range
<Appendix 1. Signal Characterizer (SC) Block>A1-5IM 01S01C01-01ENA1.4 List of Signal Characterizer Block ParametersRelative Index Paramet
<Appendix 1. Signal Characterizer (SC) Block>A1-6IM 01S01C01-01ENA1.5 Application ExampleA1.5.1 Input CompensationThe following is an app
<Appendix 1. Signal Characterizer (SC) Block>A1-7IM 01S01C01-01ENA1.5.3 Backward Control SC: The controlled variable output from PID is co
<Appendix 2. Integrator (IT) Block>A2-1IM 01S01C01-01ENAppendix 2. Integrator (IT) BlockThe Integrator (IT) block adds two main inputs and
<Appendix 2. Integrator (IT) Block>A2-2IM 01S01C01-01ENA2.2 Input Process SectionWhen executed, the Integrator block rst performs input p
<Appendix 2. Integrator (IT) Block>A2-3IM 01S01C01-01ENA2.2.3 Converting AccumulationThis following describes an example of accumulation c