<ESpecicationsCommontoFieldMateBasicandAdvance>
E-18
IM 01R01A01-01E 9th Edition : May 31, 2013-00
Displaying Segment Viewer
IfatagandaddressaremodiedinthisTag/AddressAssignmentwindow,theSegmentViewer
window will automatically be updated, displaying updated tags/addresses.
NOTE
NotesonModifyingTagsforFOUNDATIONeldbusDevices
1. Specication
Whenatagismodied,thecommunicationconnectioninformation(VCRandLink
Object)isautomaticallycleared.ThisinformationisdenedintheFOUNDATIONeldbus
specication.
Whenatagismodied,thescheduleinformationofthefunctionblock(FB_START_
ENTRY)isautomaticallycleared.Thisinformationisdenedinthefunctionspecicationfor
communication cards of National Instruments.
To conclude: When a tag is set, the schedule information and communication connection
information are automatically cleared.
2. Yokogawa Device Operation
When the schedule information of the function block is cleared, the operation of AI Block stops
and the LCD display values (for example, a pressure value in the case of EJA) cannot indicate
the current state.
Youneedtobecareful,becausethereisapossibilitythatthedisplayedPVvalue(usually,OUTof
AIBlock)isdifferentfromtheactualvalue.YoucanconrmtheactualvalueinDeviceViewer.
In this case, function block re-scheduling is necessary.
Device Class Setting
ThisfunctionchangesthedeviceclassofaFOUNDATIONeldbusH1devicetoLinkMasteror
Basic.
Startup
Select Segment Viewer – Select Device – Action to activate Device Class Setting.
E030102E.ai
Select either Basic or Link Master.
Clicking the Set button in the above
window causes this window to
appear.
In order to reflect the device class
setting in the device, the window
prompts you to select whether to
restart the device.
Figure E-3-2 Device Class Setting