<11. Device Information>
11-2
IM 01S01C01-01EN
Table 11.2 Contents of DEVICE_STATUS_2 (index 1046)
Hexadecimal Diplay through DD Description
NAMUR
NE-107 category
0x80000000 LTB in O/S Mode LCD Transducer Block is in O/S mode C
0x40000000 LCD Failure LCD has been failing F
0x20000000 Amp Temp Out of Range Amplier temperature is out specication range S
0x00008000 MAO1 in O/S Mode MAO1 Block is in O/S mode C
0x00004000 MAO1 in Man Mode MAO1 Block is in Man mode C
0x00002000 MAO1 Not Scheduled MAO1 Block is not scheduled C
0x00000800 MAO2 in O/S Mode MAO2 Block is in O/S mode C
0x00000400 MAO2 in Man Mode MAO2 Block is in Man mode C
0x00000200 MAO2 Not Scheduled MAO2 Block is not scheduled C
0x00000080 IS1 in O/S Mode IS1 Block is in O/S mode C
0x00000040 IS1 in Man Mode IS1 Block is in Man mode C
0x00000020 IS1 Not Scheduled IS1 Block is not scheduled C
0x00000008 IS2 in O/S Mode IS2 Block is in O/S mode C
0x00000004 IS2 in Man Mode IS2 Block is in Man mode C
0x00000002 IS2 Not Scheduled IS2 Block is not scheduled C
Table 11.3 Contents of DEVICE_STATUS_3 (index 1047)
Hexadecimal Diplay through DD Description
NAMUR
NE-107 category
0x80000000 PID1 in O/S Mode PID1 Block is in O/S mode C
0x40000000 PID1 in Man Mode PID1 Block is in Man mode C
0x20000000 PID1 Not Scheduled PID1 Block is not scheduled C
0x10000000 PID1 in Bypass Mode PID1 Block is in Bypass mode C
0x08000000 PID2 in O/S Mode PID2 Block is in O/S mode C
0x04000000 PID2 in Man Mode PID2 Block is in Man mode C
0x02000000 PID2 Not Scheduled PID2 Block is not scheduled C
0x01000000 PID2 in Bypass Mode PID2 Block is in Bypass mode C
0x00080000 SC in O/S Mode SC Block is in O/S mode C
0x00040000 SC in Man Mode SC Block is in Man mode C
0x00020000 SC Not Scheduled SC Block is not scheduled C
0x00008000 IT in O/S Mode IT Block is in O/S mode C
0x00004000 IT in Man Mode IT Block is in Man mode C
0x00002000 IT Not Scheduled IT Block is not scheduled C
0x00001000 IT Total Backup Err
IT Total Backup has failed. Last IT Output.Value(IT.LAST.
VALUE) is not saved
F
0x00000800 IT Conf. Err
IT Clock Period(IT.CLOCK_PER) is smaller than IT
Period of Execution(EXECUTION_PERIOD)
C
0x00000080 AR1 in O/S Mode AR1 Block is in O/S mode C
0x00000040 AR1 in Man Mode AR1 Block is in Man mode C
0x00000020 AR1 Not Scheduled AR1 Block is not scheduled C
0x00000010 AR1 Range Conf. Err
AR1 Range High(AR1.RANGE_HI) is smaller than AR1
Range Lo(AR1.RANGE_LO)
C
0x00000008 AR2 in O/S Mode AR2 Block is in O/S mode C
0x00000004 AR2 in Man Mode AR2 Block is in Man mode C
0x00000002 AR2 Not Scheduled AR2 Block is not scheduled C
0x00000001 AR2 Range Conf. Err
AR2 Range High(AR2.RANGE_HI) is smaller than AR2
Range Lo(AR2.RANGE_LO)
C
Kommentare zu diesen Handbüchern