Yokogawa FVX110 Bedienungsanleitung Seite 141

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 164
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 140
<Appendix 5. PID Block>
A5-10
IM 01S01C01-01EN
NOTE: If a control block is connected as a cascade primary
block of the PID block in question, a mode transition of
the PID block to Cas occurs in the following sequence
due to initialization of the cascade connection: RCas or
ROut Auto Cas.
A5.18 Alarms
There are two kinds of alarms generated by a PID
block: block and process alarms.
A5.18.1 Block Alarm (BLOCK_ALM)
The block alarm BLOCK_ALM is generated upon
occurrence of either of the following errors (values
set in BLOCK_ERR) and noties the content of
BLOCK_ERR.
Value of
BLOCK_ERR
Condition
Local Override MODE_BLK actual of PID block is LO.
Input Failure IN.status of the PID block is either of
the following:
Bad-Device Failure
Bad-Sensor Failure
Out of Service MODE_BLK.target of the PID block is
O/S.
A5.18.2 Process Alarms
There are six types of process alarms. Priority level
can be set to process alarms. The priority level is
set for each process alarm type.
Process
Alarm
Cause of Occurrence
Parameter
Containing
Priority Level
Setting
HI_HI_ALM Occurs when the PV
increases above the
HI_HI_LIM value.
HI_HI_PRI
HI_ALM Occurs when the PV
increases above HI_LIM
value.
HI_PRI
LO_ALM Occurs when the PV
decreases below the
LO_LIM value.
LO_PRI
LO_LO_
ALM
Occurs when the PV
decreases below the
LO_LO_LIM value.
LO_LO_LIM
DV_HI_ALM Occurs when the value of
[PV - SP] increases above
the DV_HI_LIM value.
DV_HI_PRI
DV_LO_
ALM
Occurs when the value
of [PV - SP] decreases
below the DV_LO_LIM
value.
DV_LO_PRI
A5.19 Example of Block
Connections
PID
BKCAL_IN OUT
IN
AO
BKCAL_OUT
CAS_IN
AI
OUT
FA0506.ai
When conguring a simple PID control loop by
combining an eld device with a eldbus valve
positioner that contains an AO block, follow the
procedure below to make the settings of the
corresponding eldbus function blocks:
1. Connect the AI block and PID block of the eld
device, and the AO block of the valve positioner
as shown above.
2. Set MODE_BLK.target of the PID block to
O/S, and then set GAIN, RESET, and RATE to
appropriate values.
3. Check that the value of MODE_BLK.actual of
the AI block is Auto.
4. Set MODE_BLK.target of the AO block to
CAS|AUTO (meaning "Cas and Auto").
5. Check that the value of BKCAL_IN.status of the
PID block is not Bad.
6. Check that the value of IN.status of the PID
block is not Bad.
7. Check that Auto is set in MODE_BLK.permitted
of the PID block.
8. Set MODE_BLK.target of the PID block to Auto.
When nishing all steps in order, the PID block and
AO block exchange the respective information and
initialize the cascade connection. Consequently,
the value of MODE_BLK.actual of the PID block
changes to Auto and automatic PID control starts.
Seitenansicht 140
1 2 ... 136 137 138 139 140 141 142 143 144 145 146 ... 163 164

Kommentare zu diesen Handbüchern

Keine Kommentare