2.8 Analog/PWM Output Settings
Procedure
Setting Analog Output
1. Click Channel to show the Channel setup screen.
2. Click the AO Channel tab.
3. Select the Use check boxes for the AO channels you wish to output.
4. Specify a channel operation of Transmi
ssion Output or User Output 1 through
User Output 4. If user output is specied, you can enter settings in the monitor
screen.
Of all the
AO and PWM channels selected for user output, only one can be specied
for each channel, for a total of four.
5. When Transm
ission Output is specied, enter the reference channel. The
Reference Channel cannot be entered if the channel operation is user output.
6.
Select a range from the Range list box.
7. Click the Mi
n box or Max box under Span and enter the minimum or the maximum
value of the span.
Select the source action
Select the
output range
Transmission output reference channel
Select output or no output
Scroll to set the output action and pattern output
Minimum/Maximum value
setting for the output span
Click here
Click the AO Channel tab.
8. Click the Power ON box under Specied Output and select Hold or Preset Value.
9. Click the Error box under Specied Output and select Hold or Preset Value.
10. If you select Preset Value under
Specied Output, click Preset Value under
operation, and enter the voltage or current.
1
1. Click the Default
box under Pattern Output and select ON or OFF for the initial
operation in the loop settings.
12.
Click the Type box under
Pattern Output and select Continuous or Ti
mes.
13. If you select Times for Type under Pattern Output, click the Count box under
Pattern Output, and enter the number of loops.