2-37
IM WX103-01E
Logger
2.6 Setting Alarms
Procedure
1. Click Channel.
The Channel setup screen appears.
2. Click the
Meas. Ch tab or the Math Ch tab.
3. Select the alarm type from the Type list box under
Alarm 1 to Alarm 4.
When not using difference input on measurement channels, select OFF, High, or
Low. When using dif
ference input, select OFF, dHigh, or dLow.
On math channels, select OFF, High, Low, rHigh, or rLow.
4.
Click the
Value box, and enter the alarm value.
5. Click the Hysteresi
s box, and enter the alarm hysteresis value.
6. If you selected a rate-of-change alarm rHigh or rLow for the alarm type on a
computation channel, select the interval used to detect the rate-of-change from the
Interval of rate-of-change alarm list box.
Hysteresis of alarm 1
Alarm value of alarm 1
Alarm 1 type
Set Alarm 2 in a similar fashion
For math channels
Rate-of-change interval when the Type is set to rHigh or rLow
Hysteresis of alarm 1
Alarm value of alarm 1
Alarm 1 type
Hysteresis of alarm 2
Alarm value of alarm 2
Alarm 2 type
Click here.
Click here to set the alarm
per channel
For measurement channels
Click here to set the alarm
per channel
Scroll the screen and set alarms 3 and 4 in the same manner