8-23
IM WX104-01E
1
2
3
4
5
6
7
8
9
Index
Configuring the CX1000/CX2000
Control Function Settings
SP Tracking
Turn the target setpoint tracking ON or OFF.
PV Tracking
Turn the measurement value tracking ON or OFF.
Target Setpoint Limiter
Set the value in the measurement span EU (0.0 to 100.0%). L must be smaller than U.
Output Velocity Limiter
Select or clear the check box to turn the output velocity limiter ON or OFF, and specify a
value between 0.1 and 100.0. This is unavailable for style number S2 or later if you set
[Control Output] to [On/Off control] in the [Setup] tab for [Internal Loop].
Anti-reset Windup
Select the anti-reset windup from [Auto] or [Manual]. This is unavailable for style number
S2 if you set [Control Output] to [On/Off control] in the [Setup] tab for [Internal Loop].
Dev Band
Set the deviation band of the anti-reset windup between 50.0 and 200.0%.
This setting is only valid when the [Anti-reset Windup] is set to [Manual].
Control Groups
Set the groups to which control functions apply.
From the [Setting] tab, select [Control Group].
Group Name
Enter a group name using a maximum of 16 characters.
8.4 Control Function General Settings