<10. Parameter Summary>
10-5
IM 01C27C01-01EN
Object
ID
Attribute
ID
Label Description
Default
value
Handling
4.
TRANSDUCER
block
(continued)
11 Special Order ID Displays the special order number, if applicable. --- R
12 Unit Sel1 Selects whether to automatically apply the unit to the
word for the parameter for which the unit display is
selected, or apply the characters that are written to
Display Unit1. (Auto, Custom)
Auto W
13 Display Unit11 When Custom is selected in Unit Sel1, set the display
unit using 6 characters or less.
NULL W
14 LCD Intermittetnt
Time
*2
Set the time to turn off display on the LCD indicator.
When 0 is set, it is diplayed in continuous mode.
Unit: second
60 seconds W
15 XD Filter
*2
Set the damping time to Tranceducer value in the AI1
ans AI2 blocks.
Unit: second
When Measurement mode is set to continuous mode,
it is valid.
2 seconds W
16 Measurement
Rate
*2
Indicates the cycle to publish the measurement value
and status
0 R
5.
AI1 block
1 Process Value AL1 is a pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W
2 Block Mode A universal parameter to indicate the block’s operation
status. Each O/S, Auto, and Man can select from.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by
Target of Al object.
4. Normal : Indicate normal status mode of Al
object.
1.
Target=Auto
2.
Actual=Auto
3.
Permitted=
Auto
4.
Normal=Auto
W
3 Concentrator OID Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3 R
4 Scale Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal = 2
W
26 Tag Description A universal parameter to store the comment that
describes the tag
Al1:
Differential
Pressure
W
27 Process Value
Filter Time
Allows adjusting the time constant for ltering the PV
value. Setting unit: Second. This is enabled for the
Continuous mode.
*5
0 second W
28 Simulate Switch A simulation function switch for the AI object test
(Disable, Enable)
1 (Disable) W
29 Transducer Value When Simulate Switch is set to Disable, this value
is used as the input value for the AI object. Refer to
Figure 10.1.
Disable R
30 Simulate Value When Simulate Switch is set to Enable, this value is
used as the input value for the AI object.
The input value can be changed.
--- W
51 Upper Limit Indicates the upper limit (URL) for the pressure. --- R