User’sManualYokogawa Electric CorporationEJX210BFlange Mounted Differential Pressure TransmitterIM 01C27C01-01ENIM 01C27C01-01EN8th Edition
<2. Handling Cautions>2-2IM 01C27C01-01EN2.4 Selecting the Installation Location The transmitter is designed to withstand severe environme
<11. General Specications>11-13IM 01C27C01-01ENProcess flange size: 4 inch (100 mm)Process flange size: 3 inch (80 mm)Process flange size:
iIM 01C27C01-01ENRevision Information Title : EJX210B Flange Mounted Differential Pressure Transmitter Manual No. : IM 01C27C01-01ENEdition D
<2. Handling Cautions>2-3IM 01C27C01-01EN2.6 Restrictions on Use of Radio TransceiversIMPORTANTAlthough the transmitter has been designed
<2. Handling Cautions>2-4IM 01C27C01-01EN2.8 Installation of an Explosion-Protected InstrumentIf a customer makes a repair or modication
<2. Handling Cautions>2-5IM 01C27C01-01ENNote 4. Battery Pack USE ONLY BATTERY PACK YOKOGAWA F9915MA OR F9915NS.Note 5. Special Conditio
<2. Handling Cautions>2-6IM 01C27C01-01ENNote 2. Installation• Installation should be in accordance with local installation requirements.
<2. Handling Cautions>2-7IM 01C27C01-01EN2.8.4 IECEx CerticationCaution for IECEx Intrinsically safe type.Note 1. Model EJX Series press
<2. Handling Cautions>2-8IM 01C27C01-01EN(2) Technical DataArticle 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).(3)
<2. Handling Cautions>2-9IM 01C27C01-01ENNOTEThis equipment has been tested and found to comply with the limits for a Class A digital devic
<3. Component Names>3-1IM 01C27C01-01EN3. Component NamesCover flangeProcess connectorProcess connection(Low pressure side)BoltF0301.aiZer
<4. Installation>4-1IM 01C27C01-01EN4. Installation4.1 Precautions Before installing the transmitter, read the cautionary notes in Sectio
iIM 01C27C01-01ENEJX210BFlange Mounted Differential Pressure TransmitterIM 01C27C01-01EN 8th Edition8th Edition: Jan. 2014 (YK)All Rights Reserved, C
<4. Installation>4-2IM 01C27C01-01ENIMPORTANTDo not rotate the transmitter section more than the above limit.Pressure-detector sectionF0402
<4. Installation>4-3IM 01C27C01-01EN4.6 Mounting the Flushing Connection Ring4.6.1 Mounting to Pressure Detector SectionThe ushing conne
<4. Installation>4-4IM 01C27C01-01EN4.7 Afxing the Teon FilmThe FEP Teon option includes a teon lm and uorinated oil. Before mountin
<5. Installing Impulse Piping>5-1IM 01C27C01-01EN5. Installing Impulse Piping5.1 Impulse Piping Installation PrecautionsThe impulse pipin
<5. Installing Impulse Piping>5-2IM 01C27C01-01EN5.2 Impulse Piping Connection ExamplesFigure 5.2 shows examples of typical impulse piping
<6. Wiring>6-1IM 01C27C01-01EN6. Wiring6.1 Mounting Antenna and WiringFor Amplier housing code 8 and 9, an antenna is not attached to th
<6. Wiring>6-2IM 01C27C01-01EN6.1.2 Mounting External Antenna and Wiring Antenna Extension Cable6.1.2.1 Mounting of External AntennaMount
<6. Wiring>6-3IM 01C27C01-01ENTransmitter bodyGrounding cableProtect by self-bonding tapeF0604.aiAntenna extension cable 2: 10 mAntennaAnte
<6. Wiring>6-4IM 01C27C01-01EN6.1.2.3 Mounting of Arrester and WiringMount an arrester between the extension cables and connect the ground
<7. Operation>7-1IM 01C27C01-01EN7. Operation7.1 Preparation for Starting OperationThe EJX210B ange mounted differential pressure transm
iiIM 01C27C01-01EN4.6 Mounting the Flushing Connection Ring ... 4-34.6.1 Mounting to Pressure De
<7. Operation>7-2IM 01C27C01-01EN• Measurement range (measurement lower/upper limit, unit).7.2 Zero Point AdjustmentAfter completing prep
<7. Operation>7-3IM 01C27C01-01EN7.3 Starting OperationAfter completing the zero point adjustment, follow the procedure below to start ope
<7. Operation>7-4IM 01C27C01-01EN2) Creating a provisioning information le The following provisioned information is stored in the provisi
<7. Operation>7-5IM 01C27C01-01EN(c) Conrm connecting statusF0708.ai(d) JoinF0709.ai7.5 Shutting Down The TransmitterRemove the battery p
<7. Operation>7-6IM 01C27C01-01ENF0710.aiDrain plugWhen you loosen the drain plug, the accumulated liquid or gas will be expelled in the di
<7. Operation>7-7IM 01C27C01-01EN7.6.4 Venting Gas for Flushing Connection Ring1) Gradually open the vent screw to vent gas from the ush
<8. Setting Parameters>8-1IM 01C27C01-01EN8. Setting ParametersThis transmitter can remotely handle range changes, Tag No. setup, monitori
<8. Setting Parameters>8-2IM 01C27C01-01EN8.3 Setting Parameters8.3.1 Parameter Usage and SelectionBefore setting a parameter, please see
<8. Setting Parameters>8-3IM 01C27C01-01EN8.3.2 Function Block and Menu Tree(1) Function BlockThe function of this transmitter is shown b
<8. Setting Parameters>8-4IM 01C27C01-01ENOnline Menu (continued)• Block Info• Block Mode• Dynamic Variables• Configuration• Calibration• O
iiiIM 01C27C01-01EN8.3.8 Integral Indicator Setup ...8-198.3.9 Unit for Displayed T
<8. Setting Parameters>8-5IM 01C27C01-01ENOnline Menu (continued)• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI2 SP)
<8. Setting Parameters>8-6IM 01C27C01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI3 Temp)• Tag Description(Blo
<8. Setting Parameters>8-7IM 01C27C01-01EN(b) Detachable antenna type (Amplier housing code: 8 or 9)• Configuration• Diagnostics• Alerts•
<8. Setting Parameters>8-8IM 01C27C01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Calibration• Others(AI1 DP)• Tag Desc
<8. Setting Parameters>8-9IM 01C27C01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI2 SP)• Tag Description(Block
<8. Setting Parameters>8-10IM 01C27C01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI3 Temp)• Tag Description(Bl
<8. Setting Parameters>8-11IM 01C27C01-01EN(2) Menu TreeThe menu tree of the device conguration tool of our recommendation is shown below
<8. Setting Parameters>8-12IM 01C27C01-01EN• Configure/Setup(AI2 SP)F0803-2.ai• Tag Description(Block Info)• Upper Limit• Lower Limit• PV R
<8. Setting Parameters>8-13IM 01C27C01-01EN• Transducer Value. Status• Transducer Value. Value• UAPMO(Diagnostic)F0803-3.ai• Device Diagn
<8. Setting Parameters>8-14IM 01C27C01-01EN(b) Detachable antenna type (Amplier housing code: 8 or 9)• UAPMO• TRANSDUCER• AI1 DP• AI2 SP•
<1. Introduction>1-1IM 01C27C01-01EN1. IntroductionThank you for purchasing the DPharp EJX Differential Pressure transmitter.Your EJX Pres
<8. Setting Parameters>8-15IM 01C27C01-01EN• Configure/Setup(AI2 SP)F0803-5.ai• Tag Description(Block Info)• Upper Limit• Lower Limit• PV R
<8. Setting Parameters>8-16IM 01C27C01-01EN• Transducer Value. Status• Transducer Value. Value• UAPMOMenu (Online)(continued)(Diagnostic)
<8. Setting Parameters>8-17IM 01C27C01-01EN8.3.3 Parameters for Wireless Communication(1) Network InformationConcentrator object block :
<8. Setting Parameters>8-18IM 01C27C01-01ENNOTEWhen the device detects AL01 and AL02, the LCD display stays on regardless of the status in
<8. Setting Parameters>8-19IM 01C27C01-01EN8.3.7 Output Signal Low Cut Mode SetupLow cut mode can be used to stabilize the output signal n
<8. Setting Parameters>8-20IM 01C27C01-01EN8.3.9 Unit for Displayed TemperatureWhen the instrument is shipped, the temperature units are s
<8. Setting Parameters>8-21IM 01C27C01-01ENb. To match current input and output value, follow procedureLike tank level measurement that is
<8. Setting Parameters>8-22IM 01C27C01-01EN(2) Span AdjustmentSpan Adjustment is function to change the input and output characteristic th
<8. Setting Parameters>8-23IM 01C27C01-01EN8.3.12 Software Write ProtectionHardware write protection and software write protection function
<8. Setting Parameters>8-24IM 01C27C01-01EN8.4 Self-Diagnostics8.4.1 Identify Problems by Using the Device Conguration ToolFirst, check
<1. Introduction>1-2IM 01C27C01-01EN1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the syst
<8. Setting Parameters>8-25IM 01C27C01-01EN8.4.2 Alert ReportEJX generates alert information related to Diagnostic Status and automaticall
<8. Setting Parameters>8-26IM 01C27C01-01ENTable 8.5 Diagnostic Results SummaryDiagnostic Status ContentsAlertTypeNAMUR NE107 CategoryDiag
<8. Setting Parameters>8-27IM 01C27C01-01EN8.4.3 Checking with Integral IndicatorNOTEIf an error is detected by running self-diagnostics,
<9. Maintenance>9-1IM 01C27C01-01EN9. Maintenance9.1 OverviewWARNING Since the accumulated process uid may be toxic or otherwise harmfu
<9. Maintenance>9-2IM 01C27C01-01ENTable 9.1 Instruments Required for CalibrationName Yokogawa-recommended Instrument RemarksProvisioning
<9. Maintenance>9-3IM 01C27C01-01ENTable 9.2 Tools for Disassembly and ReassemblyTool Quantity RemarksPhillips screwdriver1 JIS B4633, No
<9. Maintenance>9-4IM 01C27C01-01ENZeroadjustmentscrewRF assemblyCPU assemblyAmplifer coverMounting screwIntegral indicatorBossStudF0902.ai
<9. Maintenance>9-5IM 01C27C01-01ENIMPORTANTConrm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior
<9. Maintenance>9-6IM 01C27C01-01ENCAUTIONWhen replacing the batteries, be sure to replace the two batteries at the same time and do not us
<9. Maintenance>9-7IM 01C27C01-01ENrequirements before shipping. When transporting this transmitter with the battery pack inserted, keep it
<1. Introduction>1-3IM 01C27C01-01EN1.2 Radio WaveIMPORTANT- This instrument is equipped with a wireless module which is designated as a
<9. Maintenance>9-8IM 01C27C01-01ENAbnormalities appear in measurement.: Areas where self-diagnostic offers supportIs process variableitsel
<9. Maintenance>9-9IM 01C27C01-01ENConnect the device configuration tool and check self-diagnostics.Does the self-diagnostic indicate probl
<9. Maintenance>9-10IM 01C27C01-01EN9.5.3 Errors and CountermeasuresTable 9.3 Error Message Summary (Causes and Actions)Integral indicato
<9. Maintenance>9-11IM 01C27C01-01ENIntegral indicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status Detail CauseRelease/recov
<9. Maintenance>9-12IM 01C27C01-01ENIntegral indicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status Detail CauseRelease/recov
<9. Maintenance>9-13IM 01C27C01-01ENTable 9.4 Error Message Summary (Output Actions)Integral IndicatorFactory NAMUR categoryBitDiagnostic
<9. Maintenance>9-14IM 01C27C01-01ENIntegral IndicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status DetailOutput actionsPress
<9. Maintenance>9-15IM 01C27C01-01ENIntegral IndicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status DetailOutput actionsPress
<10. Parameter Summary>10-1IM 01C27C01-01EN10. Parameter SummaryTable 10.1 ParameterObjectIDAttribute IDLabel DescriptionDefaultvalueHand
<10. Parameter Summary>10-2IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling1.UAPMO block(continued)105 Power Suppl
<1. Introduction>1-4IM 01C27C01-01EN1.5 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<10. Parameter Summary>10-3IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling1.UAPMO block(continued)121 Faults Sens
<10. Parameter Summary>10-4IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling3.COblock(continued)4 PUB_ITEM_MAX Maxi
<10. Parameter Summary>10-5IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling4.TRANSDUCERblock(continued)11 Special
<10. Parameter Summary>10-6IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling5.AI1 block (continued)52 Lower Limit I
<10. Parameter Summary>10-7IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling5.AI1 block (continued)107 T Zero Cmp P
<10. Parameter Summary>10-8IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling6.AI2 block (continued)53 PV Range Sets
<10. Parameter Summary>10-9IM 01C27C01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling7.AI3 block(continued)2 Block Mode A un
<10. Parameter Summary>10-10IM 01C27C01-01ENTable 10.2 Diagnostic Status Detail[0]Bit Diagnostic Status Detail DescriptionDiagnostic Statu
<11. General Specications>11-1IM 01C27C01-01EN11. General Specications11.1 Standard SpecicationsCommunication protocol: ISA100.11a pro
<11. General Specications>11-2IM 01C27C01-01ENZero Adjustment Limits:Zero can be fully elevated or suppressed, within the lower and upper
<2. Handling Cautions>2-1IM 01C27C01-01EN2. Handling CautionsThis chapter provides important information on how to handle the transmitter.
<11. General Specications>11-3IM 01C27C01-01ENWetted Parts Materials: High pressure side: Refer to “Model and Sufx Codes.”Flushing conne
<11. General Specications>11-4IM 01C27C01-01EN11.2 Model and Sufx Codes● InstructionThe model and sufx codes for EJX210B consist of tw
<11. General Specications>11-5IM 01C27C01-01ENII. Flange mounting section (Flush type)● Precess ange size: 3-inch (80 mm)T02E.aiDescrip
<11. General Specications>11-6IM 01C27C01-01ENII. Flange mounting section (Flush type)● Precess ange size: 2-inch (50 mm)T03E.aiDescrip
<11. General Specications>11-7IM 01C27C01-01ENII. Flange mounting section (ush type)● Precess ange size: 1 1/ 2-inch (40 mm)T04E.aiDes
<11. General Specications>11-8IM 01C27C01-01ENII. Flange mounting section (Extended type)● Precess ange size: 4-inch (100 mm)T05E.aiThe
<11. General Specications>11-9IM 01C27C01-01ENII. Flange mounting section (Extended type) ● Precess ange size: 3-inch (80 mm)T06E.aiDes
<11. General Specications>11-10IM 01C27C01-01EN11.3 Optional Specications OPTIONAL SPECIFICATIONS (For Explosion Protected type) Item
<11. General Specications>11-11IM 01C27C01-01EN OPTIONAL ACCESSORIESProduct Part number SpecicationBattery pack assembly F9915NQ Batter
<11. General Specications>11-12IM 01C27C01-01EN11.4 Dimensions Flush type (Amplifier housing code 7) No ring (Flushing connection ring