<8. Setting Parameters>
8-26
IM 01C27C01-01EN
Table 8.5 Diagnostic Results Summary
Diagnostic Status
Contents
Alert
Type
NAMUR
NE107
Category
Diagnostic Status Detail Description
Faults in electronics 78 F
AMP_T_SENSOR_FAIL* Amplier temperature sensor failure
AMP_EEPROM_FAIL Amplier EEPROM failure
AMP_EEP_IRREGULAR AMP EEPROM version not correct
G_A_COMM_FAIL G/A failure
FC_DELTA_T_FAIL C-side delta T circuit failure
FR_DELTA_T_FAIL R-side delta T circuit failure
WL_AD_FAIL
Battery voltage not detected (AMP
failure)
Faults in sensor or actuator
element
77 F
FC_SENSOR_FAIL C sensor frequency failure
FR_SENSOR_FAIL R sensor frequency failure
CAP_T_SENSOR_FAIL Capsule temperature sensor failure
CAP_EEPROM_FAIL Capsule EEPROM failure
CAP_EEP_IRREGULAR CAP EEPROM version not correct
FC_UNOSC_FAIL C sensor oscillation stop failure
FR_UNOSC_FAIL R sensor oscillation stop failure
Installation, calibration
problem
76 C
DP_TRIM_SPAN_OUTSIDE
"Pressure span adjustment variable
outside of range"
DP_TRIM_ZERO_OUTSIDE
"Pressure zero adjustment variable
outside of range"
SP_TRIM_SPAN_OUTSIDE
"Static pressure span adjustment
variable outside of range"
SP_TRIM_ZERO_OUTSIDE
"Static pressure zero adjustment
variable outside of range"
LCD_OUTSIDE_LIMIT LCD display outside of limits
Out of service 75 O
AI1_OUT_OF_SERVICE AI1 O/S mode
AI2_OUT_OF_SERVICE AI2 O/S mode
AI3_OUT_OF_SERVICE AI3 O/S mode
Outside sensor limits 74 C
DP_OUTSIDE_LIMIT Pressure outside of range
SP_OUTSIDE_LIMIT Static pressure outside of range
CAPT_OUTSIDE_LIMIT Capsule temperature outside of range
AMPT_OUTSIDE_LIMIT Amplier temperature outside of range
Environmental conditions
out of device specication.
73 O
DP_OUTSIDE_RANGE Pressure setting outside of range
SP_OUTSIDE_RANGE
Static pressure setting outside of
range
Power is critical low:
maintenance need short-
term.
71 M
WL_DEEPSLP_ALM * Deep sleep due to low battery
CRITICAL_LOWBAT ** Deep sleep due to low battery
Power is low:
maintenance need mid-term
70 M WL_LOWBAT_ALM Low battery
Simulation is active 68 C
AI1_SIMULATION_ACTIVE AI1 Simulation mode
AI2_SIMULATION_ACTIVE AI2 Simulation mode
AI3_SIMULATION_ACTIVE AI3 Simulation mode
Not applicable for the diagnostic regarding AI2 object and static pressure measurement.
*: Applicable for Integral antenna type (Amplier housing code: 7).
**: Applicable for Detachable antenna type (Amplier housing code: 8 or 9).