4.19 Setting A/D Converter Integration Time, Filter,
and Scan Interval
Open the A/D Converter Integration Time, Filter, and Scan Interval setting screen (see
below) as follows:
Click the SETUP tab and select Interval from the SETUP (Basic) Setting contents box,
or select from the menubar Settings > SETUP (Basic) Settings > and then either, A/D
Converter Integration Time, Filter, Scan Interval, or File of Retransmission Output.
Select a SETUP topic Setup tabSelect A/D converter time
Filter ON/OFF
Measurement scan interval
Set the time constant
A/D Converter Integration Time
Select the A/D converter integration time for each unit. Select it from the following:
Auto: the frequency of 50/60 Hz is automatically switched corresponding to the power
frequency of this instrument. Note that Auto does not function for the stand-alone DC
power supply model or for extended types using a DC power supply subunit.
50 Hz: the integration time is set to 20 ms (50 Hz).
60 Hz: the integration time is set to 16.7 ms (60 Hz).
100 ms: the integration time is set to 100 ms (10 Hz)
The default setting is AUTO. However, if the instrument is a stand-alone DC power
supply model, the default setting is 20 ms (50 Hz).
Filter
Set the filter to reduce normal mode noise, ON or OFF.
Scan Interval
The duration of time (one scan) in which the measurement of all channels is carried
out, is called the scan interval.
This interval can be set to any value from 0.5 second to 60 seconds. The shortest is
40 ch/500 ms for the stand-alone model, or 300 ch/500 ms for the expandable model
(varies with the shortest measurement period of the input module).