1-11
IM WX102-01E
Before Operation
• Resistance temperature detector (RTD)
RTD Type Display Measurable Range
Pt100:1mA PT1 –200.0 to 600.0°C
Pt100:2mA PT2 –200.0 to 250.0°C
JPt100:1mAJ JPT1 –200.0 to 550.0°C
JPt100: 2mAJ JPT2 –200.0 to 250.0°C
Pt50: 2mAJ PT50 –200.0 to 550.0°C
Ni100:1mA-S
*1
NI1 –200.0 to 250.0°C
Ni100:1mA-D
*2
NI2 –60.0 to 180.0°C
Ni120:1mA
*3
NI3 –70.0 to 200.0°C
Cu10: GE
*4
CU1 –200.0 to 300.0°C
Cu10: L&N
*4
CU2 –200.0 to 300.0°C
Cu10: WEED
*4
CU3 –200.0 to 300.0°C
Cu10: BAILEY
*4
CU4 –200.0 to 300.0°C
Pt100:1mA-H PT1S –140.00 to 150.00°C
Pt100: 2mA-H PT2S –70.00 to 70.00°C
JPt100:1mA-H JPT1S –140.00 to 150.00°C
JPt100: 2mA-H JPT2S –70.00 to 70.00°C
J263*B J263B –0.0 to 300.0K
*1
RTD (SAMA)
*2 R
TD (DIN)
*3 RTD (McGROW EDISON COMPANY)
*4 RTD (Cuid)
Guaranteed accuracy range Cu10: GE –84.4 to 170.0°C
Cu10: L&N –75.0 to 150.0°C
Cu10: WEED –20.0 to 250.0°C
Cu10: BAILEY –20.0 to 250.0°C
• Contact point (DI)
Input Type Display Measurable Range
VOLT LEVL 0 to 1
*1
CONTACT CONT 0 to 1
*2
*1 OFF if below 2.4V, ON if above 2.4V
*2 Contact point ON/OFF
• mA input (mA)
Measurement Range Display Measurable Range
20mA 20mA –20.000 to 20.000mA
• Pulse input (PULSE)
Measurement Range Measurable Range
RATE Determine the count number during 1s interval.
GATE Determine the most occurring state, ON or OFF, during 1s
interval.
• Power monitor (AC)
Input Range Display
250V-0.5A 250V-0.5A
250V-5A 250V-5A
25V-0.5A 25V-0.5A
25V-5A 250V-5A
• Strain input (STRAIN)
Measurement Range Display Measurable Range
2k 2k –2000.0 to 2000.0µε
20k 20k –20000 to 20000µε
200k 200k –20000 to 20000µε
1.5 DA100 Functions