• Scale/span (SCALE)
For VOLT, TC, RTD, DI, mA, AC and STRAIN, scale conversion is possible. Scale
conversion is to convert measured values into values (physical values) of the
system of units suitable for the application. The values obtained by converting the
predetermined lower limit and upper limit values for span into physical value for the
application will be used as the lower limit and upper limit values for scale. The unit for
scale-converted values can be set using six characters.
Also, the scaling display mode/span of PULSE is set on the ra
nge screen. The span is
the lower/upper limits of pulse count/ON time.
Count number/s
0
3000
0
100
rpm
Upper Span
Lower Scale
Lower Span
Upper Scale
Number of
revolutions
Setting the measurement range
Relationship between input type, measurement range and measurable range is given
below.
• DC voltage input (VOLT)
Measurement Range Display Measurable Range
20mV 20mV –20.000 to 20.000mV
60mV 60mV –60.00 to 60.00mV
200mV 200mV –200.00 to 200.00mV
2V 2V –2.0000 to 2.0000V
6V 6V –6.000 to 6.000V
20V 20V –20.000 to 20.000V
50V 50V –50.00 to 50.00V
• Thermocouple (TC)
TC Type Display Measurable Range
R Type R 0.0 to 1760.0°C
S Type S 0.0 to 1760.0°C
B* Type B 0.0 to 1820.0°C
K Type K –200.0 to 1370.0°C
E Type E –200.0 to 800.0°C
J Type J –200.0 to 1100.0°C
T Type T –200.0 to 400.0°C
N Type N 0.0 to 1300.0°C
W Type W 0.0 to 2315.0°C
L Type L –200.0 to 900.0°C
U Type U –200.0 to 400.0°C
KpAu7Fe KP 0.0 to 300.0K
*
Guaranteed accuracy range Type-B 400.0 to 1820.0°C
1.5 DA100 Functions