Setting the Scale (Only When Scaling)
8.
Select the Use check boxes under Scale to enable changing of the scale.
9.
Select the decimal point position from the Point list box for Scale.
10.
Click the Min box or Max box under Scale and enter the minimum or the maximum
value of the scale.
11.
Click the Unit box and enter the unit of the scaled value.
Setting the Reference Channel for Difference Input (Valid Only When Measuring
the Difference with Respect to the Measured Value of the Reference Channel)
12.
Select the Use check box under Difference Input.
13.
Select the reference channel for the difference input from the Ref. Ch. list box
under Delta.
Setting the Remote RJC Reference Channel (Valid Only When the Input Mode Is
Set to RRJC (TC)
14.
Select the reference channel for the remote RJC from the Ref. Ch. list box under
RRJC.
Note
If moving from the Channel screen to the Display Setup or Monitor screen, if the differential
input reference channel or remote RJC reference channel setting is inappropriate the following
message appears.
Yes: Disable measurement channels with inappropriate settings (clear the Monitor check box in
the Channel screen) and move to the Display Setup or Monitor screen
No: Change the settings of the measurement channels with inappropriate settings without
moving to the next screen
Message
Setting the Time Constant of the First-Order Lag Filter (Valid Only When the
Input Mode Is Set to Something Other than DI)
15.
Select the time constant from the Filter list box.
Setting the Burnout (Valid Only When the Input Mode Is Set to TC)
16.
Select the direction in which the measured value is set off the range (+OVER or
–OVER) when a burnout occurs from the Burnout list box.
Setting the RJC (When the Input Mode Is Set to TC)
17.
Click the Type box under RJC and select Internal or External.
18.
If you select External, click the Volt box under RJC and enter the compensation
voltage.
2.4 Setting the Measurement Conditions (Setting the Measurement Channels)