Seitenansicht 117
4-7
IM MX180-01E
Calibrator
3
2
1
4
5
App
Index
3.
After making the connections according to the explanation given on the calibration
execution screen 1, click the Calibrate button.
For the 8-CH Medium Speed Analog Output module, after entering settings
according to the explanation given on the calibration execution screen 1, click the
Calibrate button.
The figure below is an example of the 4-CH, High-Speed Universal Input Module.
Exp. Calibration executi
on screen 1
Start calibration
Return to the previous screen
Return to the Unit Information screen
The figure below is an example of the 8-CH, Medium-Speed Analog Output
Module.
Exp. Calibration executi
on screen 1
Start calibration
Return to the previous screen
Return to the Unit Information screen
Click the Calibrate button.
The message, “Calibrating. Please wait and do not perform any other operation.” appears.
When the calibration completes successfully, the calibration execution screen 2 appears.
4.2 Calibration Procedure