<3.INSTALLATION>
3-4
IM 01E25D11-01EN
• Conrmationofsealingconditionsforthe
owmeter
Conrm that the terminal box screw and wiring ports
are well sealed. Equip the conduit piping with drain
plugs or waterproof glands to prevent moisture or
water from penetrating into the owmeter through
the conduit.
• Regularinspections
Inspect the sealing conditions as mentioned above,
and the inside of the terminal box at least once a
year. Also, due to rain, etc. when it is suspected
that water may have penetrated into the inside
owmeter perform supplementary inspections.
3.2.2 FlowmeterPiping
CAUTION
Misaligned or slanted piping can lead to leakage
and damage to the anges.
(1) Correct any misaligned or slanted piping, and
any gaps that may exist between mounting
anges before installing the owmeter (refer to
Figure 3.2.2).
Slanted
F0308.ai
Misaligned
Figure3.2.2 SlantedandMisalignedFlowmeter
Piping
(2) Inside a newly installed pipeline, there may
be some foreign substances such as residue
from welding or wood chips. Remove them
by ushing the piping before mounting the
owmeter. This prevents the lining from
being damaged, as well as the occurrence
of erroneous measured signals resulting
from foreign substances passing through the
owtube during measurement.
3.3 MountingProcedures
CAUTION
When attaching optional grounding rings to
the owtube with lining material natural hard
rubber or uorocarbon PTFE, gaskets must be
placed between each grounding ring and the
owtube. Fluid leakage will happen without these
gaskets. These gaskets are to be supplied by
customer. Do not forget those gaskets also when
ordering and attaching the grounding rings later
additionally.
NOTE
The tightening torque value varies depending
on the type of lining and gasket as shown in the
tables in this section.
IMPORTANT
Use bolts and nuts in compliance with the ange
ratings. When choosing the gaskets, be sure to
choose sheet gaskets designed tot for ange
standard.
(1) MountingDirection
Mount the owmeter so that the ow direction of
the uid to be measured is in line with the direction
of the arrow mark on the owmeter. It may be
especially difcult to move large size owtubes after
bringing them into the pit. Check directions before
bringing.
IMPORTANT
If it is impossible to match the direction of
the arrow mark, the direction of the electrical
connection can be changed. Refer to Section 5.1
to do this properly.
In case the uid being measured ows against
the arrow direction, refer to the parameter J20:
FlowDirection in the user’s manual of the
AXFA11 Magnetic Flowmeter Remote Converter
(IM 01E20C01-01E).