<7. Operation>
7-2
IM 01C25B01-01E
Vent plug (Fill plug)
Tap valve
Stop valve
Drain valve
F0702.ai
Figure 7.1b Liquid Pressure Measurement
Conrming that Transmitter is Operating
Properly
Using the BT200
If the wiring system is faulty, ‘communication
error’ appears on the display.
If the transmitter is faulty,SELF CHECK
ERROR’ appears on the display.
communication error
PARAM
C60:SELF CHECK
ERROR
Communication error
(Faulty wiring)
Self-diagnostic error
(Faulty transmitter)
DATA DIAG PRNT ESC
F0703.ai
Figure 7.2 BT200 Display
Using the integral indicator
If the wiring system is faulty, the display stays
blank.
If the transmitter is faulty, an error code is
displayed.
Self-diagnostic error on the integral indicator
(Faulty transmitter)
F0704.ai
Figure 7.3 Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on
the display of the integral indicator or the
communicator, refer to subsection 8.5.3 for the
corrective action.
Verify and Change Transmitter Parameter
Setting and Values
The parameters related to the following items are
set at factory as specied in order.
Calibration range
Integral indicator display
Output mode
Software damping (optional)
Other parameters like following are shipped with the
default setting.
Low-cut
Process alarm setting
Static pressure range
Signal characterizer
Write protection
To conrm or change the values, see IM 01C25T01-
06EN or 01C25T03-01E.
7.2 Zero Point Adjustment
After completing preparations for operating the
transmitter, adjust the zero point.
Zero point adjustment can be done by turning the
transmitters zero-adjustment screw or by using
the communicator. This section describes the
procedure for the zero-adjustment screw. For the
communicator procedure, see the communication
manual.
IMPORTANT
Do not turn off the power to the transmitter
immediately after performing a zero point
adjustment. Powering off within 30 seconds of
performing this procedure will return the zero
point to its previous setting.
NOTE
Before performing this adjustment, make sure
that the external zero adjustment function has
NOT been disabled by a parameter setting.
To check the output signal, use a digital multimeter,
calibrator, or communicator.