User’sManualDPharpBRAIN Communication Type(EJXA, EJAE)IM 01C25T03-01EIM 01C25T03-01E5th Edition
<3. Operation>3-2IM 01C25T03-01Eb. Entering Alphabetic CharactersPress either the left or right shift key and then an alphanumeric key to e
<3. Operation>3-3IM 01C25T03-01E3.1.3 Calling Up Menu Addresses Using the Operating KeysDATA DIAG PRNT ESCPARAM A60:SELF CHECK GOODCOD
<3. Operation>3-4IM 01C25T03-01E3.2 Setting Parameters Using the BT200 3.2.1 Parameter Usage and SelectionBefore setting a parameter, ple
<3. Operation>3-5IM 01C25T03-01E3.2.2 Menu TreeA: DISPLAYHOMEA10: OUTPUTA11: PRESA15: OUTPUT mAA16: ENGR. OUTPUTA17: ENGR. EXPA20: SP %*1A
<3. Operation>3-6IM 01C25T03-01E3.2.3 Setting ParametersSet or change the parameters as necessary. After completing these, do not fail to
<3. Operation>3-7IM 01C25T03-01Eb. Setting Calibration Range Lower Range Value and Upper Range Value (C21: PRES LRV, C22: PRES URV)These r
<3. Operation>3-8IM 01C25T03-01E(4) Output Mode and Integral Indicator Display Mode Setup (C40: OUTPUT MODE, I20: P DISP MODE)The mode set
<3. Operation>3-9IM 01C25T03-01EThe low cut point has hysteresis so that the output around the point is behaved as below gure. <Example
<3. Operation>3-10IM 01C25T03-01Ea. Display Selection (I10: DISP OUT1)Select the variable for the parameter I10: DISP OUT1 to display on th
<3. Operation>3-11IM 01C25T03-01Ed. Setting Static Pressure Unit and Scale (D30: SP UNIT, D33: SP LRV, and D34: SP URV)Static pressure can
iIM 01C25T03-01EDPharpBRAIN Communication TypeIM 01C25T03-01E 5th Edition5th Edition: June 2013 (YK)All Rights Reserved, Copyright © 2004, Yokogawa E
<3. Operation>3-12IM 01C25T03-01EStandard specicationsThe burnout direction switch is set to HIGH. If a failure occurs, the transmitter ou
<3. Operation>3-13IM 01C25T03-01E(12) Output Status Setup when a Hardware Error Occurs (D26: ERROR OUT)This parameter allows the setting of
<3. Operation>3-14IM 01C25T03-01ENote that changing the upper range value does not cause the lower range value to change but does change th
<3. Operation>3-15IM 01C25T03-01EFEED NO OKSET J11:P ZERO ADJ 0.00000 kPaCLRDEL ESCSET J11:P ZERO ADJ 0.00000 kPa + 0A pres
<3. Operation>3-16IM 01C25T03-01Eb-1. Auto Sensor Trim• Example: For the range of 10 to 30 kPa. FEED NO OKSET J11:P ZERO ADJ 10.0000 kP
<3. Operation>3-17IM 01C25T03-01Ec. Sensor Trim for Static Pressure (J21: SP ZERO ADJ, J22: SP SPAN ADJ, J25: SP ZERO DEV, J26: SP SPAN DE
<3. Operation>3-18IM 01C25T03-01E• Example: Set the number of coodinates on the line graph to 5.ESCCLRSET T11:NUM OF POINT
<3. Operation>3-19IM 01C25T03-01E• Example: Set the status output to output an off signal when the input pressure exceeds 75 kPa with
<3. Operation>3-20IM 01C25T03-01ETransmitterLh0H(+)● EJX118A/EJA118EF0353.aihhLLHTransmitterTransmitter0(+)(–)● EJX438A/EJA438ENote: When t
<3. Operation>3-21IM 01C25T03-01E3.3.2 Display Transmitter Model and SpecicationsThe BT200 can be used to display the model and specicat
iiIM 01C25T03-01E(10) CPU Failure Burnout Direction and Hardware Write Protect . 3-11(11) Software Write Protect ...
<4. Self-diagnostics>4-1IM 01C25T03-01E4. Self-diagnostics4.1 Checking for Problems4.1.1 Identifying Problems with BT200The following fo
<4. Self-diagnostics>4-2IM 01C25T03-01E4.1.2 Checking with Integral IndicatorNOTEIf an error is detected by running self-diagnostics, an e
<4. Self-diagnostics>4-3IM 01C25T03-01EIndicator BT200 display CauseOutput operation during errorCountermeasureAL. 50P. LRV50: P ILLEG LRV
<5. Parameter Summary>5-1IM 01C25T03-01E5. Parameter SummaryInstruments to which applicable:F: Differential pressure transmittersP: Absolu
<5. Parameter Summary>5-2IM 01C25T03-01ENo. Parameter name Item*1R/WContent Default valueApplicable modelUploaddataF P LD AUX SET 1 Auxilia
<5. Parameter Summary>5-3IM 01C25T03-01ENo. Parameter name Item*1R/WContent Default valueApplicable modelUploaddataF P LG ALARM SET Alarm s
<5. Parameter Summary>5-4IM 01C25T03-01ENo. Parameter name Item*1R/WContent Default valueApplicable modelUploaddataF P LJ ADJUST Adjusting
<5. Parameter Summary>5-5IM 01C25T03-01ENo. Parameter name Item*1R/WContent Default valueApplicable modelUploaddataF P LM22 GASKET MATL Gas
<Appendix 1. Safety Instrumented Systems Installation>A1-1IM 01C25T03-01EAppendix 1. Safety Instrumented Systems InstallationWARNING The c
<Appendix 1. Safety Instrumented Systems Installation>A1-2IM 01C25T03-01ETable A1.2 Proof TestingTesting method Tools required Expected ou
<1. Introduction>1-1IM 01C25T03-01E1. IntroductionThank you for purchasing the DPharp EJX series pressure transmitter/EJA series pressure
<Appendix 1. Safety Instrumented Systems Installation>A1-3IM 01C25T03-01EA1.3 Denitions and AbbreviationsA1.3.1 DenitionsSafetyFreedom
iIM 01C25T03-01ERevision Information Title : DPharp BRAIN Communication Type Manual No. : IM 01C25T03-01EEdition Date Page Revised Item1st A
<1. Introduction>1-2IM 01C25T03-01E(a) Installation• This instrument may only be installed by an engineer or technician who has an expert
<1. Introduction>1-3IM 01C25T03-01E1.3 ATEX DocumentationThis section is only applicable to the countries in the European Union.GBDKIENLSF
<2. Connection>2-1IM 01C25T03-01E2. ConnectionThe BRAIN communication signal is superimposed onto the 4 to 20 mA DC analog signal. Since t
<2. Connection>2-2IM 01C25T03-01E2.4 Integral Indicator Display When Powering OnFor models with the integral indicator code “D”, the disp
<3. Operation>3-1IM 01C25T03-01E3. OperationThe transmitter is equipped with BRAIN communications capabilities, so that range changes, Tag