<2. Handling Cautions>
2-7
IM 01C25B01-01E
Explosion-proof for Class I, Groups B, C and
D.
Dustignition-proof for Class II/III, Groups E, F
and G.
Enclosure: NEMA TYPE 4X
Temperature Code: T6...T4
Ex d IIC T6...T4
Enclosure: IP66/IP67
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Ambient Temperature: –50* to 75°C (T4),
–50* to 8C (T5), –50* to 75°C (T6)
* –15°C when /HE is specied.
Supply Voltage: 42 V dc max.
Output Signal: 4 to 20 mA dc
Note 2. Wiring
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
In hazardous location, wiring shall be in
conduit as shown in the gure.
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALÀ
MOINS DE 50cm DU BOÎTIER.
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
SUPPLY
PULSE
CHECK
ALARM
Transmitter
F0205-1.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
SUPPLY
PULSE
CHECK
ALARM
Transmitter
F0205-2.ai
All wiring shall comply with local installation
requirements and local electrical code.
In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
Unused apertures shall be closed with
suitable ameproof certied blanking
elements. (The plug attached is ameproof
certied.)
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
QUAND LA TEMPÉRATURE AMBIANTE
65°C, UTILISEZ DES CÂBLES
SISTANTES Á LA CHALEUR 90°C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation of
America is prohibited and will void Canadian
Standards Explosionproof Certication.
c CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters
with optional code /CU1 or /V1U1 can be
selected the type of protection (CSA Intrinsically
Safe or CSA Explosionproof) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.