- 98/131 -
IM MW100-S16E-1
Ed01
2.5.11. DNP slave/server object table setting (WV)
This command is used to configure object table of DNP slave/server. For
implementing DNP communication functions, this command is added.
WV p1, p2, p3, p4, p5
27
p1 : Object type (IO_B, IO_A, MATH_B, MATH_A,
COM_B, COM_A)
IO_BI : Binary Input object for I/O channels
IO_AI : Analog Input object for I/O channels
IO_BO : Binary Output object for I/O channels
IO_AO : Analog Output object for I/O channels
MATH_BI : Binary Input object for Math channels
MATH_AI : Analog Input object for Math channels
COM_BO : Binary Output object for Comm. channels
COM_AO : Analog Output object for Comm. channels
p2 : Top channel number to map (001 to 060,
A001 to A300, C001 to C300)
001 to 060 : in case p1 is IO_xx
A001 to A300 : in case p1 is MATH_xx
C001 to C300 : in case p1 is COM_xx
p3 : Mapping data count (0 to 60, 0 to 300)
0 to 60 : in case p2 is 001 to 060
0 to 300 : in case p2 is A001 to A300 or C001 to C300
p4 : Event class (NONE, 1 to 3)
NONE : does not generate event
1 to 3 : assign Class 1 to 3
27
Unless DNP option is specified, command can't be used.