IM MW100-S16E-1
Ed01
Table 17. Parameters for enabling DNP slave function
Kind Configuration
Function Choice of serial function (driver)
- select ”DNP 3.0 Slave”
5
Address DNP address of DNP slave function
- configurable within 0 to 65519
Table 18. Parameters for enabling DNP server function
Kind Configuration
Server DNP address of the DNP server function
- configurable within 0 to 65519
TCP Keep Alive Period of TCP keep alive
- ignored (not used at DNP server)
Application
Timeout
Application service timeout
- ignored (not used at DNP server)
Action Enabling switch of server function
- selectable from ”On”, “Off”
Port Service port of the server
- configurable within 1 to 65535
6
5
If user choose other functions except for DNP DNP 3.0 Slave, DNP slave function will be
stopped.
6
Well-known ports for DNP 3.0 protocol are 20000/tcp and udp.