Table 30. Parameters for configuring DNP application service
Kind Configuration
Client DNP address of the DNP client function
- configurable within 0 to 65519
Server DNP address of the DNP server function
- configurable within 0 to 65519
Unsolicited
Message
Enabling switch for permitting unsolicited message at DNP slave/server
- toggle switch to "Enable" or not
Timestamp Enabling switch for putting timestamp into event data at DNP slave/server
- toggle switch to "Put" or not
Relative Time Enabling switch for using relative time as timestamp at DNP slave/server
- toggle switch to "use" or not
Select Time Holding time of Select message at DNP slave/server
- configured within 1 to 60 [s]
Event Buffer Size Event buffer size prepared to each object in the object table
- configurable within 1 to 100
Delay Time Delay time from event happening to reporting
- configurable within 0 to 60 [s]
Event Count Maximum event count contained into a single unsolicited message
- configurable within 1 to 100
Analog Deadband Deadband applied to Analog Input and Analog Output objects
- configurable within 1 to 10000