User’sManualDPharpHART 5/HART 7 Communication Type(EJXA, EJAE)IM 01C25T01-06ENIM 01C25T01-06EN4th Edition
<2. Connection>2-1IM 01C25T01-06EN2. Connection2.1 Integral Indicator Display When Powering OnFor models with the integral indicator cod
<2. Connection>2-2IM 01C25T01-06EN(a) Conrmation on the name plate The last numerical number engraved after Serial number and year of pr
<2. Connection>2-3IM 01C25T01-06EN● Conrmation by using HART conguration tool a) Connect the conguration tool to the transmitter. b)
<2. Connection>2-4IM 01C25T01-06EN2.5 Interconnection Between DPharp and the HART Conguration ToolThe HART conguration tool can interfac
<3. Parameter Setting>3-1IM 01C25T01-06EN3.1 Menu TreeThe structure of menu tree varies according to conguration tool based on DD or DTM.
<3. Parameter Setting>3-2IM 01C25T01-06ENBF0301-03.ai: HART 7 only: EJX Series only• Diag/Service• Test device (DD)• Status (DTM) • Loop Te
<3. Parameter Setting>3-3IM 01C25T01-06ENB1 • Diag ParametersF0301-04.ai• Ratio fDP Status• Ratio fDP• Ratio fSPl Status• Ratio fSPl• Rat
<3. Parameter Setting>3-4IM 01C25T01-06EN• Basic setup• Tag• Long tag• Unit• Re-range• Device infomation• Xfer fnctn• Pres Damp• Low cut• L
<3. Parameter Setting>3-5IM 01C25T01-06ENSee ESee D1(next page)• Detailed setup• Review• Sensors• Signal condition• Output condition• Displ
<3. Parameter Setting>3-6IM 01C25T01-06END1F0301-07.ai: HART 5 only: HART 7 only: EJX Series onlySame as aboveSame as above• Burst Variable
iIM 01C25T01-06ENDPharpHART 5/HART 7 Communication Type(EJXA, EJAE)IM 01C25T01-06EN 4th Edition4th Edition: June 2013 (YK)All Rights Reserved,
<3. Parameter Setting>3-7IM 01C25T01-06EN• Detailed setup• Review• Sensors• Signal condition• Output condition• Display condition• Device i
<3. Parameter Setting>3-8IM 01C25T01-06EN3.1.2 Group II: EJX HART 5 DTM based on FDT1.2F0301-21.aiRoot Menu• Process Variables• Device Sta
<3. Parameter Setting>3-9IM 01C25T01-06ENF0301-22.ai• Diag and Service• Service• Advanced Diag Variables• Advanced Diag Configurations• Adv
<3. Parameter Setting>3-10IM 01C25T01-06ENF0301-23.ai• ConfigurationT• Pressure Sensor• Static Pressure Sensor• Physical Information• Proce
<3. Parameter Setting>3-11IM 01C25T01-06ENF0301-24.ai• Trim Who• Trim Date• Trim Loc• Trim Desc• Pres Zero trim• P UTP• P LTP• P UTD• P LTD
<3. Parameter Setting>3-12IM 01C25T01-06EN3.2 Basic SetupIMPORTANTAfter setting and sending data with the HART conguration tool, wait 30
<3. Parameter Setting>3-13IM 01C25T01-06EN3.2.3 Range ChangeThe range values are factory-set as specied by the customer. To change the ra
<3. Parameter Setting>3-14IM 01C25T01-06EN• Procedure to call up the Quick resp displayDD and DTM (excluding EJX_HART 5[1.2])[Root Menu]
<3. Parameter Setting>3-15IM 01C25T01-06EN3.2.8 Static Pressure SetupThe differential pressure transmitter can display the static pressure
<3. Parameter Setting>3-16IM 01C25T01-06EN3.3.2 Analog Output Signal Adjustable RangeOutput signal adjustable range at normal operating co
iiIM 01C25T01-06EN3.3.3 Integral Indicator Display Mode ...3-163.3.4 Integral Indicator Scale Se
<3. Parameter Setting>3-17IM 01C25T01-06ENa. Display SelectionAt Disp select, select the variable that the parameter Disp Out 1 will disp
<3. Parameter Setting>3-18IM 01C25T01-06EN Setting by EJX HART 5 DTM based on FDT1.2User can input the desired unit at Engr Unit.• Proce
<3. Parameter Setting>3-19IM 01C25T01-06EN(2) Full Sensor Trim—Auto Trim and Manual Trim Full sensor trim is carried out by performing Aut
<3. Parameter Setting>3-20IM 01C25T01-06EN• Procedure to call up the display for pressureDD and DTM (excluding EJX_HART 5[1.2])[Root Menu]
<3. Parameter Setting>3-21IM 01C25T01-06EN3.3.9 CPU Failure Burnout Direction and Hardware Write ProtectThere are two slide switches on th
<3. Parameter Setting>3-22IM 01C25T01-06EN3.3.11 Signal CharacterizerThis function is used to compensate the output for non-linear applica
<3. Parameter Setting>3-23IM 01C25T01-06EN(2) Threshold Level SettingSet the threshold of high and low alert value for alarm generation.•
<3. Parameter Setting>3-24IM 01C25T01-06ENNOTENo status output signal has been dened for a CPU failure or hardware error. Use a 4-20 mA si
<3. Parameter Setting>3-25IM 01C25T01-06ENTransmitterLh0H(+)● EJX118A/EJA118EF0310.aihhLLHTransmitterTransmitter0(+)(–)● EJX438A/EJA438ENot
<3. Parameter Setting>3-26IM 01C25T01-06EN Setting by EJX HART 5 DTM based on FDT1.2Call up the test output parameter (Loop test) and sel
iiiIM 01C25T01-06EN4.2.3 Heat Trace Monitoring...4-214.2.3.1 Flg Temp Coef Settin
<3. Parameter Setting>3-27IM 01C25T01-06EN• Procedure to call up the Squawk display[Root Menu] → Diag/Service → Test (DTM)/Test device (DD
<3. Parameter Setting>3-28IM 01C25T01-06ENTable 3.1 Burst parametersCommand parameter Burst CommandBurst Msg Trigger ModeBurst Trigger Sou
<3. Parameter Setting>3-29IM 01C25T01-06EN(2) Burst mode setting procedure• Procedure to call up the displayDD and DTM [Root Menu] → Det
<3. Parameter Setting>3-30IM 01C25T01-06ENa. Burst CommandSelect the transmission data at Burst Command parameter.Burst Command Command pa
<3. Parameter Setting>3-31IM 01C25T01-06ENe. Burst ModeWhen the Burst mode is set to “Wired HART Enabled”, the transmitter starts to send
<3. Parameter Setting>3-32IM 01C25T01-06ENb) Acknowledge Event NoticationExecute Acknowledge Event Notication method.1) Set to Enter Eve
<3. Parameter Setting>3-33IM 01C25T01-06EN3.3.17.2 Setting on HART 7HART 7“Multidropping” transmitters refer to the connection of several t
<3. Parameter Setting>3-34IM 01C25T01-06EN2) Activate the “Chg universal rev” methodIMPORTANTThe message is displayed to separate the tra
<4. Diagnostics>4-1IM 01C25T01-06EN4. Diagnostics4.1 Self-Diagnostics4.1.1 Identify Problems by Using HART Conguration ToolThe HART co
<4. Diagnostics>4-2IM 01C25T01-06EN4.1.2 Checking with Integral IndicatorNOTEIf an error is detected by running self-diagnostics, an error
<1. Introduction>1-1IM 01C25T01-06EN1. IntroductionThank you for purchasing the DPharp EJX series pressure transmitter/EJA series pressure
<4. Diagnostics>4-3IM 01C25T01-06EN(5) Conguration Change CounterThe Conguration Change Counter is incremented once for every user actio
<4. Diagnostics>4-4IM 01C25T01-06EN Pressure Measurement• Operational pressure is near outside of diagnostic range.• Even though pressu
<4. Diagnostics>4-5IM 01C25T01-06EN Functional block diagramThe gure below shows the functional block diagram of ILBD.EJXSensorProcess V
<4. Diagnostics>4-6IM 01C25T01-06EN4.2.2.1 Blockage Detection Limit parameterWhen the parameter based on pressure uctuation exceeds the
<4. Diagnostics>4-7IM 01C25T01-06ENTable 4.3 Default Values of Limit Parameter# ParameterDifferential pressure transmitterFlange mounted d
<4. Diagnostics>4-8IM 01C25T01-06EN4.2.2.2 Combination of Reference Result and Blockage Detection Diag ApplicableThe transmitter can det
<4. Diagnostics>4-9IM 01C25T01-06ENRef fDP: OKRef fSPI: OKRef fSPh: OKRef BlkF: OKFluctuation Parameters• Test for low-pressure side •
<4. Diagnostics>4-10IM 01C25T01-06ENNOTEWhen setting ILBD parameters in the transmitter via “Online Parameter” of the EJX HART 5 DTM based
<4. Diagnostics>4-11IM 01C25T01-06EN4.2.2.4 Operating ProcedureThe basic ow of the ILBD operation is as follows.1) Initial setting2) Cond
<4. Diagnostics>4-12IM 01C25T01-06ENBitDD (HART 5/HART 7) DTM (HART 7)DTM (HART 5) Category0Not used Not used1Not used Not used2A Blockin
<1. Introduction>1-2IM 01C25T01-06EN1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the syst
<4. Diagnostics>4-13IM 01C25T01-06EN<Example>When the level range that can be measured by the transmitter with 100 kPa span is –80 to
<4. Diagnostics>4-14IM 01C25T01-06EN• Procedure to call up the displayDD and DTM (excluding EJX_HART 5[1.2])[Root Menu] → Diag/Service → D
<4. Diagnostics>4-15IM 01C25T01-06ENTable 4.4 Requirements to apply ILBDConditionfDP 7×10-10 or morefSPI 1×10-10 or morefSPh 1×10-10 or mo
<4. Diagnostics>4-16IM 01C25T01-06EN Invalid Ref F, SPH, SPL, or DPWhen the enough reference uctuation value is not obtained, an alarm o
<4. Diagnostics>4-17IM 01C25T01-06EN4.2.2.10 TuningWhen the pressure uctuation amplitude in uids is not sufciently large or an alarm is
<4. Diagnostics>4-18IM 01C25T01-06ENCombination of threshold for sensitivity parameterHigh Medium LowLim fDPmax 1.503.00 3.00Lim fDPmin 0.4
<4. Diagnostics>4-19IM 01C25T01-06EN4.2.2.12 ILBD Parameter List# Parameter name Default value Explanation1 Diag Error 0x0000 The results d
<4. Diagnostics>4-20IM 01C25T01-06EN# Parameter name Default value Explanation28 Ref fSPl Value of fSPl obtained under normal condition.29
<4. Diagnostics>4-21IM 01C25T01-06EN4.2.3 Heat Trace MonitoringThe transmitter with Heat trace monitoring function calculates the ange te
<4. Diagnostics>4-22IM 01C25T01-06ENAmplifier TemperatureCapsule TemperatureAmp tempSnsr tempFlg Temp CoefFlg tempExecution HTMCT+(CT-AT) x
<1. Introduction>1-3IM 01C25T01-06EN1.3 Abbreviation and MarkingThe following models, HART protocol revisions and conguration les are ap
<4. Diagnostics>4-23IM 01C25T01-06EN4.2.3.3 Parameter Lists for Heat Trace Monitoring# Parameter name Default value Explanation1 Diag Erro
<4. Diagnostics>4-24IM 01C25T01-06EN4.3 Alarms and CountermeasuresTable 4.5 Alarm Message SummaryIntegral indicator HART conguration to
<4. Diagnostics>4-25IM 01C25T01-06ENIntegral indicator HART conguration tool display Cause4-20mA Output operation during error Counter
<4. Diagnostics>4-26IM 01C25T01-06ENIntegral indicator HART conguration tool display Cause4-20mA Output operation during error Counter
<4. Diagnostics>4-27IM 01C25T01-06ENTable 4.6 HART Conguration Tool Error MessagesError message Probable cause Countermeasure Invalid sel
<4. Diagnostics>4-28IM 01C25T01-06ENTable 4.10 Relationship between Alarm and Status available for HART 7Integral IndicatorHART congurati
<4. Diagnostics>4-29IM 01C25T01-06ENIntegral IndicatorHART conguration tool displayDevice StatusExtended Device StatusValue and Status (D
<4. Diagnostics>4-30IM 01C25T01-06ENIntegral IndicatorHART conguration tool displayDevice StatusExtended Device StatusValue and Status (D
<4. Diagnostics>4-31IM 01C25T01-06ENIntegral IndicatorHART conguration tool displayDevice StatusExtended Device StatusValue and Status (D
<5. Parameter Summary>5-1IM 01C25T01-06EN5. Parameter SummaryFunction Label Item Contents Default value Handling *1Analog output AO alm ty
<1. Introduction>1-4IM 01C25T01-06EN1.4 Applicable Conguration Files DDFile Applied deviceFile nameDD revision()ModelHART protocol rev
<5. Parameter Summary>5-2IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Device informationChg universal rev Change t
<5. Parameter Summary>5-3IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Diag Lim Lim fDPmax Upper limit for Ratio f
<5. Parameter Summary>5-4IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Display setup Bar Indicator Bar indicator Of
<5. Parameter Summary>5-5IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Event NoticationEvent Notication Retry Tim
<5. Parameter Summary>5-6IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Fluct Variables fDP Average value of the su
<5. Parameter Summary>5-7IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Process Alerts Temp Hi Alert Val High alert
<5. Parameter Summary>5-8IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1Process variablesTV (DD)Snsr temp (DTM)Tempe
<5. Parameter Summary>5-9IM 01C25T01-06ENFunction Label Item Contents Default value Handling *1SP setup A/G Select Gauge/Abs select for sta
<Appendix1. Safety Instrumented Systems Installation>A1-1IM 01C25T01-06ENAppendix 1. Safety Instrumented Systems InstallationWARNING The c
<Appendix1. Safety Instrumented Systems Installation>A1-2IM 01C25T01-06ENTable A1.2 Proof TestingTesting method Tools required Expected ou
<1. Introduction>1-5IM 01C25T01-06EN1.5 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<Appendix1. Safety Instrumented Systems Installation>A1-3IM 01C25T01-06ENA1.3 Denitions and AbbreviationsA1.3.1 DenitionsSafety Freedo
<Appendix2. ILBD Check List>A2-1IM 01C25T01-06ENAppendix 2. ILBD Check ListFill out the below checklist according to the operation ow of
<Appendix2. ILBD Check List>A2-2IM 01C25T01-06ENChecklist (2/5)No. Items Parameters Result Example8Alarm status• Check the alarm status sh
<Appendix2. ILBD Check List>A2-3IM 01C25T01-06ENChecklist (3/5)Go to the following step according to the result of "Invalid Ref xx&quo
<Appendix2. ILBD Check List>A2-4IM 01C25T01-06ENChecklist (4/5)No. Items Parameters Result Example10-a-2L Side Blocking• Close the low-pre
<Appendix2. ILBD Check List>A2-5IM 01C25T01-06ENChecklist (5/5)No. Items Parameters Result Example10-b Simulation of Blockage detection ope
iIM 01C25T01-06ENRevision Information Title : DPharp HART 5/HART 7 Communication Type (EJXA, EJAE) Manual No. : IM 01C25T01-06ENEdit