Viewing and Creating Setup Data
Setting the Modbus Master
Data type
Select whether or not use command.
Register No. (slave device)
Address (slave device)
Communication input data (DX100P: C01 to C12,
DX200P: C01 to C30)
• Basic
Read cycle: The cycle at which data is read from other devices. Select the read cycle
from [125 ms], [250 ms], [500 ms], [1 s], [5 s], [2 s], or [10 s]
Timeout:SpecifyatimeperiodthattheDXPwaitsforaresponsefromthespecied
slave device after transmitting a command. Select the timeout time from [125 ms], [250
ms], [500 ms], [1 s], [5 s], [2 s], [10 s], or [1 min].
Retrials: The number of times to retransmit the command when there is no response
fromthespeciedslavedevice.Selectthenumberofretrialsfrom[Off](0),[1],[2],[3],
[4], [5], [10] or [20].
• Type
• INT16:16-bitsignedinteger
• UINT16:16-bitunsignedinteger
• INT32_B:“32-bitsignedinteger”isassignedtotheModbusregisterintheorder
upper 16 bits followed by the lower 16 bits.
• INT32_L:“32-bitsignedinteger”isassignedtotheModbusregisterintheorder
lower 16 bits followed by the upper 16 bits.
• UINT32_B:“32-bitunsignedinteger”isassignedtotheModbusregisterintheorder
upper 16 bits followed by the lower 16 bits.
• UINT32_L:“32-bitunsignedinteger”isassignedtotheModbusregisterintheorder
lower 16 bits followed by the upper 16 bits.
• FLOAT_B:“32-bitoating-pointdata”isassignedtotheModbusregisterinthe
order upper 16 bits followed by the lower 16 bits.
• FLOAT_L:“32-bitoating-pointdata”isassignedtotheModbusregisterinthe
order lower 16 bits followed by the upper 16 bits.