7-7
IM 04L31A01-17E
7
Response
Setting Data/Basic Setting Data
The FE command is used to output the data.
The setting/basic setting data are output in the order of the listed commands in the
table in section 6.2, “A List of Commands.” However, the setting information for the
following commands is not output.
Setting commands (setup)
SD/FR command
Setting commands (control)
All commands from UD to CM
Basic setting commands
XE, YO, YI, and YC commands
The output format of the setting/basic setting data conforms to the syntax of each
command.
Some commands are output in multiple lines. Commands that are specified for each
channel are such commands.
Syntax
The two-character command name and the succeeding parameters are output in the
following syntax.
EA
CRLF
ttsss...s
CRLF
..............
EN
CRLF
tt Command name(SR, SA..., XA, XI...)
sss...s Setting, basic setting data (variable length, one line)
Example
EA
SR01,VOLT,20mV,0,20
SR02,VOLT,20mV,0,20
...................
EN
7.2 Output Format of ASCII Data