7. OPERATION VIA HART COMMUNICATOR
Hot key 1. Span
ADMAG SE :
Flow units
1 Flow unit Cum
2 Time unit h
DEL SAVE HOME ENTER
1
2
Press Hot key.
Select “Span”.
Enter “20.0” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
Return to the presious display by pressing or .
ADMAG SE :
Span
1 Cum/h
1
HELP DEL ESC ENTER
3
Call up “Span” setting display.
ADMAG SE :
Hot key
1 Span 1 Cum/h
2 Enable write
3 New password
DEL SAVE ESC ENTER
ADMAG SE :
Span
1 Cum/h
20.0
DEL DEL ESC ENTER
4
F4
5
(ENTER)
F2
(SEND)
‘20.0’
ADMAG SE :
Hot key
1 Span 20.0Cum/h
2 Enable write
3 New password
DEL SEND ESC ENTER
When the span is set in engineering units using the ADMAG SE front panel key
switches, consideration should be given to the least significant digit which is to be
displayed for all ranges on the rate indicator of the ADMAG SE (parameter A20
FLOW RATE). For example, if the flow rate value is to be displayed to three decimal
places, set the span as “20.000” as opposed to “20.”
NOTE