5. FUNCTION AND DATA SETTINGS
5.5.7 Limiting Current Output
(1) 4 to 20mA Low Cut Output (Current output nearby 0% range)
This function makes it possible to reduce fluctuations in the 0% region to reduce it to
0%.
Display Description
Default : 00
Output
Set value
Setting range: 0 to 10% Default:0(%)
0.5%0.5%
4mA
Hysteresis:1% fixed
5.6mA(10%)
(2) 4 to 20mA Low Limit
This function limits the low end of the analog output.
The default value is set at –20%, and –10% as reverse flow limit. Please set in case
other setting is required.
2.4mA or less output in alarming is also limited.
Display Description
Default : -20(%)
Output
4mA
Setting Range: –20 to 100%
Default: –20%
5.6mA(10%)
(3) 4 to 20mA High Limit
This function limits the high end of the analog output.
The default value is set at 120%, and please set in case other setting is required.
21.6mA or more output in alarming is also limited.
Display Description
Default : 120(%)
Output
18.4mA (90%)
Setting Range: 0 to 120%
Default: 120%
4mA