<3. Operation>
3-9
IM 01C25T03-01E
The low cut point has hysteresis so that the output
around the point is behaved as below gure.
<Example>
Output mode: Linear
Low cut mode: Zero
Low cut: 20.00%
F0319.ai
Setting range: 0 to 20%
2% 2%
4mA
Output Low cut point
Input
Hysteresis
fixed at 10%
of the cut point
7.2mA
(20%)
(6) Integral Indicator Scale Setup
The followingve displays are available for integral
indicators: input pressure*
1
, % of range, user
set scale, input static pressure, and % of static
pressure range*
1
. A cycle of up to four displays can
be shown by assigning variables to the parameters
I10 to I13: DISP OUT1 to DISP OUT4.
F0320.ai
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Input static pressure
(SP)*
1
% of static pressure range
(SP %)*
1
Indicates values of input pressure
with the indication limits -32000 to
32000.
Indicates input pressure in -2.5 to
110% range depending on the
measuring range (C21, C22).
Indicates values depending on the
engineering range (I33, I34) with
the unit (I30).
Indicates input static pressure with
the indication limits -32000 to
32000.
Reference pressure is factory-set
in absolute.
Indicates input static pressure in
-10 to 110% range depending on
the measuring range (D33, D34).
A11:PRES
456 kPa
Description
and related parameters
A10:OUTPUT
45.6 %
A16:ENGR.OUTPUT
20.5 m3/min
A17:ENGR.EXP
×100
A21:SP
4.000 MPa
A20:SP %
52.6 %
*1: Available for differential pressure transmitter.
See (a.) through (d.) for each setting procedure.