3-6
<Toc> <Ind> <3. PC Link Communication >
IM 77J01J11-01E
3.2.2 BRD Reading I Relays on a Bit-by-bit Basis
Function
Reads a sequence of contiguous ON/OFF statuses by the specified number of bits starting
at a specified I relay number.
The number of bits to be read at a time is 1 to 256.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function. When performing
communication without a checksum, do not include the 2-byte checksum command
element in the command.
Command/Response (for normal operation)
Command
Element
STX Address
number
(ADDRESS)
CPU
number
01
0 BRD ETX CRI relay
number
Comma
or space
Number
of bits
(n)
Checksum
OK d1 d2 d3 ETX CRResponse
Element
STX Address
number
(ADDRESS)
CPU
number
01
dn Checksum
The response is 0 when the status is OFF or 1 when ON.
Number of Bytes
1 2 2 2111 1 2 1 1
Number of Bytes 12 2135 13 2 11
dn: reads data of the specified number of bits (n=1 to 256)
dn=0(OFF)
dn=1(ON)
030206E.EPS
Example:
Reading the status of alarm-1 of the VJ Series signal conditioner with communication
address-1.
The following command reads the status of alarm-1 (I0009) at communication address-1.
[Command]
[STX]01010BRDI0009,00199[ETX][CR]
The following response is returned with respect to the above command. (Alarm-1 is ON.)
[Response]
[STX]0101OK18D[ETX][CR]
Alarm has been ON since "1" was returned.
030207E.EPS