<Toc> <Ind> <5. MODBUS Communication >
5-5
IM 77J04J11-01E 1st Edition : 2006.08.25-00
03 Reads data from multiple D registers
Function
Reads the contents of a sequence of contiguous D registers by the specified number of D
registers, starting at a specified D register number.
The maximum number of D registers to be read at a time is 64.
For the format of response in the event of failure, see subsection 5.2.2.
Message (for normal operation)
Number of bytes in RTU mode
Number of bytes in ASCII mode
None 1 1 2
4122
Error
Check
2
End of Message
Mark (CR+LF)
None
Element Start of
Message Mark
(:)
Address
Number
(ADR)
Function
Code (03)
D-Register
Start Number
Number of
D Registers
2
4
22
Message (continued)
Response (for normal operation)
Response (continued)
Element Start of
Message Mark
(:)
Address
Number
(ADR)
Function
Code (03)
Byte
Count
Contents of
D Register
Number of bytes in RTU mode None 1 1 1 2
12 224Number of bytes in ASCII mode
Contents of
D Register
Error
Check
End of Message
Mark (CR+LF)
None22
224