3-18
<Toc> <Ind> <3. PC Link Communication >
IM 77J04J11-01E 1st Edition : 2006.08.25-00
WRM Monitors D registers and I relays on a word-by-word basis
Function
Reads the register data that have been specified in advance by the WRS command.
Before executing this command, the WRS command must always be executed to
specify which registers are to be monitored. If no register has been specified, error
code 06 is generated.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 2 1 1
Number of Bytes
12 2244 4 2 11
Command
element
STX Address
number
(ADR)
CPU
number
01
Checksum0 WRM ETX CR
Response
element
STX OK dddd1 dddd2 ETX CRAddress
number
(ADR)
CPU
number
01
ddddn Checksum
The response is returned in a 4-digit character string (0000 to FFFF) in hexadecimal.
ddddn: read data of the number of words specified by the WRS command
ddddn is a character string in hexadecimal.
n=1 to 32
Example:
Monitoring the alarm-1 setpoint (D0101) and alarm-2 setpoint (D0102) of the M Series with
address number 01.
(This command reads the registers specified by the WRS command.)
[Command]
[STX]01010WRME8[ETX][CR]
CPU number: 01
The alarm-1 setpoint 500 (01F4 [HEX]) and alarm-2 setpoint 500 (01F4 [HEX]) are re-
turned with respect to the above command (50.0 is expressed as 500).
[Response]
[STX]0101OK01F401F412[ETX][CR]