Yokogawa FieldMate Bedienungsanleitung Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 22
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
App.-2
IM 01R01A15-01EN
2nd Edition : 2013.11.07-00
Appendix B NE 107 Parameters for
FOUNDATION fieldbus
The added NAMUR NE 107 parameters for FOUNDATION fieldbus devices and item
names used in this software are shown below.
Table Appendix B-2
Parameters (NE 107)
Details
Item Name
FD_FAIL_ALM
FD_CHECK_ALM
FD_MAINT_ALM
FD_OFFSPEC_ALM
Indicate alarms which should notify Host
Alarm Broadcast
FD_FAIL_MASK
FD_CHECK_MASK
FD_MAINT_MASK
FD_OFFSPEC_MASK
Set alarms which should notify Host
Alarm Mask
FD_FAIL_ACTIVE
FD_CHECK_ACTIVE
FD_MAINT_ACTIVE
FD_OFFSPEC_ACTIVE
Indicate aggregated devices alarms
Alarm Indication
FD_FAIL_MAP
FD_CHECK_MAP
FD_MAINT_MAP
FD_OFFSPEC_MAP
Set NE 107 classification of aggregated devices
alarms
Alarm Map
FD_FAIL_PRI
FD_CHECK_PRI
FD_MAINT_PRI
FD_OFFSPEC_PRI
Set priority whether should notify Host
Alarm Priority
FD_EXTENDED_ACTIVE_n
Indicate all device alarms related to NE 107
Detailed Field
Diagnostics Alert
FD_EXTENDED_MAP_n
Set NE 107 classification of all device alarms related
to NE 107
Escalation Enable
FD_RECOMMEN_ACT
Indicates an alarm and action which the user should
do
Recommended
Action
FD_SIMULATE
Enable/Disable simulation of NE 107
Simulation
FD_VER
Version information of this specification
FD_VER
Seitenansicht 20