Power Supply
(Zone 2 only)
Transmitter
Supply
Nonhazardous Location
[Installation Diagram]
Hazardous Location
+
–
+
–
F0209.EPS
Ratings of the Power Supply as follows;
Maximum Voltage: 30 V
CENELEC ATEX Type of Protection “Dust”
[When combined with II 2G]
Follow the installation instructions described in 'b.
CENELEC ATEX Flameproof Type.'
• Applicable Standard: EN61241-0:2006, EN61241-
1:2004
• Type of Protection and Marking Code: II 2D Ex tD
A21 IP6X
• Maximum Surface Temperature:
T85°C (Tamb.: –40* to 75°C, Tp:85°C), T100°C
(Tamb.: –40* to 80°C, Tp:100°C), and T120°C
(Tamb.: –40* to 75°C, Tp:120°C)
*–15°C when /HE is specified.
Note 1. Installation instructions
The cable entry devices and blanking elements
shall be of a certificated type providing a level
of ingress protection of at least IP6X, suitable
for the conditions of use and correctly installed.
[When combined with II 1G]
Follow the installation instructions described in 'a.
CENELEC ATEX Intrinsically Safe Type.'
• Applicable Standard: EN50281-1-1:1997
• Type of Protection and Marking Code: II 1D
• Maximum Surface Temperature:
T65°C (Tamb.: 40°C), T85°C (Tamb.: 60°C), and
T105°C (Tamb.: 80°C)
Note 1. Installation instructions
The cable entry devices and blanking elements
shall be of a certificated type providing a level
of ingress protection of at least IP6X, suitable
for the conditions of use and correctly installed.
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in hazardous locations.
( III )
Tag plate for flameproof type
Tag plate for flameproof, intrinsically safe type,
type n protection, and Dust
F0298.EPS
D
T65⬚C (Tamb.: 40⬚C), T85⬚C (Tamb.: 60⬚C),and T105⬚C (Tamb.: 80⬚C)
AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP. ⱖ70⬚C, USE THE HEAT-RESISTING
CABLESⱖ90⬚C. SEE USER'S MANUAL BEFORE USE.
SEE USER'S
MANUAL
Tamb. ⫺40(⫺15) TO 60⬚C
TEMP.CLASS/MAX SURFACE TEMP.
T6/T85⬚C
T5/T100⬚C
T4/T120⬚C
CAUTION
D
, Ex tD A21 IP6X T85⬚C,T100⬚C,T120⬚C
ENCLOSURE:IP67
Tamb. ⫺40(⫺15) TO
KU21
Tamb. ⫺40(⫺15) TO 75⬚C(T6 and T4)
AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP. ⱖ70⬚C, USE THE HEAT-RESISTING
CABLESⱖ90⬚C. SEE USER'S MANUAL BEFORE USE.
⫺40(⫺15) TO 80⬚C(T5)
CAUTION
KF21