Yokogawa DR240 Bedienungsanleitung Seite 139

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 293
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 138
8-1
IM DR232-01E
8
Setting, Displaying and Recording Alarms
8.1 Setting Alarms and Relays (including internal
switches)
D I S P M O D E
P R I N TF U N C
I N S D E L
R A N G E A L A R M
S E TC H A R T E N T E R
F E E D
M. F U N C 1
M. F U N C 2
R E C O R D
00101:1/OFF
1=OFF 2=OFF 3=OFF 4=OFF
>
E S C
Press the [ALARM] key to enter the ALARM menu.
Select / set
using the keys.
To escape from a lower menu, press the MODE (ESC) key. Its main menu will appear,
although new settings / selections will not be kept.
New settings/selections will be kept when you rach the final display of that setting.
001-01:1/OFF
>Select Channel No.
001-01:1/OFF
>Select Channel No.
001-01:1/OFF
1 2 3 4
001-01:1/OFF
***SET OK***
001-01:1/H_=_ _ _0.00
001-01:1/H_=_ _ _0.00
>Alarm Limit(0.00~100.00)
RELAY=OFF
***SET OK***
RELAY=S01
RELAY=S01
***SET OK***
ENTER
ENTER
ENTER
ESC
ESC
ESC
ENTER
(Main menu)
(Lower menu)
Selecting channel Nos.
Channels Nos. A01 to A60 are available for computation channels (optional).
Selecting the alarm item number
Set the alarm item number for each channel as follows:
Select any number from among 1, 2, 3, and 4.
Alarm numbers 1 to 4 can be set for one channel.
For details on setting the alarm printout, see Section 6.5, Setting the Alarm Printout on page
6-10.
Note
If SKIP is selected for the input type or if the computation channels are OFF, alarms cannot be set.
If the following cases, the alarm is set to OFF:
If the input type or measuring range in the related channel is changed,
If computation channels are turned ON/OFF or the computation equation is changed.
If the recording span for the linear scaling, or linear scaling values is changed, or
If the standard channel for differential computation between channels is changed.
Setting the alarm or relay (including internal switches) gives more functions to this recorder. For details,
see Section 9.1, Setting Event and Action Functions on page 9-1.