IM 01C21B01-01E
8-4
8. BRAIN TERMINAL BT200 OPERATION
8.3 Setting Parameters Using the BT200
8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110A, EJA120A, and EJA130A
P: Pressure transmitters EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
L: Liquid level transmitters EJA210A and EJA220A
No. Description
Model+capsule type
Tag number
Applica-
bility
PLF
01
02
T0805.EPS
Rewrita-
bility
16 alphanumerics
GOOD/ERROR
Remarks
Item
MODEL
TAG NO.
Self-diagnostic result
03 SELF CHECK
Measured data displayA
–5 to 110%*
3
Menu nameDISPLAY
Output (in %)A10 OUTPUT (%)
–19999 to 19999Output (in engineering
units)
A11 ENGR.
OUTPUT
Unit specified in D30Amplifier temperatureA20 AMP TEMP
Unit specified in D30Capsule temperatureA21 CAPSULE
TEMP
Sensor typeB
16 uppercase alphanumerics
Menu nameSENSOR
TYPE
Model+spanB10 MODEL
Style numberB11 STYLE NO.
–32000 to 32000Lower range-limitB20 LRL
–32000 to 32000
Upper range-limitB21 URL
–32000 to 32000Minimum spanB30 MIN SPAN
Unit specified in D31*
1
Static pressureA30 STATIC
PRESS
–32000 to 32000Input (indicated as the
value after zeroing)
A40 INPUT
GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP RANGE*
1
, OVER TEMP (CAP),
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER
Self-diagnostic
messages
A60 SELF CHECK
Maximum static
pressure*
6
B40
Same as A60
MAX STAT.P.
Self-diagnostic
messages
B60 SELF CHECK
Setting dataC
16 alphanumerics
Menu nameSETTING
Tag numberC10 TAG. NO.
Selected from mmH
2
O, mmAq,
mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
,
inH
2
O, inHg, ftH
2
O, psi, or atm
Measurement range
units
C20 PRESS UNIT
–32000 to 32000(but within
measurement range)
Measurement range,
lower range value
C21 LOW RANGE
Self-diagnostic
messages
C60 Same as A60SELF CHECK
–32000 to 32000(but within
measurement range)
Measurement range,
higher range value
C22 HIGH
RANGE
Selected from 0.2*
2
, 0.5, 1.0, 2.0,
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Damping time constantC30 AMP
DAMPING
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Output mode and
integral indicator mode
C40 OUTPUT
MODE
0.0 to 20.0%
LINEAR/ZERO
Low cutD10 LOW CUT
Low cut modeD11 LOW CUT
MODE
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
Display selectionD20 DISP SELECT
Auxiliary setting data 1D Menu nameAUX SET 1
Default Value
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2.0 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.
8 uppercase
alphanumerics
Engineering unit for
display
D21 DISP UNIT
10.0%
LINEAR
–5.0 to 110.0%
Lower output range-limit
D15 OUT LIMIT(L) –5.0%*
1
–5.0 to 110.0%
Upper output range-limit
D16 OUT LIMIT(H) 110.0%
–19999 to 19999Engineering range,
lower range value
D22 DISP LRV
–19999 to 19999Engineering range,
higher range value
D23 DISP HRV
As specified when ordered.
As specified when ordered.
As specified when ordered.
deg C/deg FTem perature setting
units
D30 TEMP UNIT deg C
*1: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.