10/17
4. Communication Commands
4.1.Setting the Input Range
When setting p2=SKIP
SR p1,p2<terminator>
When p2=COM
When p6=OFF
SR p1,p2,p3,p4,p5,p6<terminator>
When p6=DELTA
SR p1,p2,p3,p4,p5,p6,p7<terminator>
When p6=SCALE
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10<terminator>
When Setting Channels to SKIP
Syntax SR p1,p2<terminator>
p1 Channel range (001–060)
p2 Input mode (SKIP)
Query SR[p1]?
Example) Set channel 1 to SKIP.
SR 001,SKIP
Explanation) Channels set to SKIP are not measured.
Specify measurement channels on p1.
When Setting Channels to COM
When no computation performed
Syntax SR p1,p2,p3,p4,p5,p6<terminator>
p1 Channel range (001–060)
p2 Input mode (COM)
p3 Measurement range (CAN)
p4 Lower limit of span (-30000–30000)
p5 Upper limit of span (-30000–30000)
p6 Computation mode (OFF)
Query SR[ p1]?
Example) Set the input type for channels 1–10 to COM(CAN), the lower limit
span to 0, and the upper limit of span to 10000.
SR 01-10,COM,CAN,0,10000,OFF
Explanation) Specify measurement channels on p1.
Kommentare zu diesen Handbüchern