3-10
IM 04L41B01-03E
• Loading Display and Event Data
Even when in batch overview mode, you can use the following procedure to load
display or event data and display the corresponding historical trend.
MENU (to switch to setting mode), and select the File tab > Load display data or
Load event data > press the CF or USB soft key > select the le and press DISP/
ENTER
T
ake note of the following points regarding loading of data.
• Y
ou can load any batch group’s data.
• The historical trend is displayed on batch group 1’s historical trend screen. When
the display is split into two windows, batch group 1’s trend is displayed as the
current trend.
• If you select Exit from the display selection menu and nish displaying the historical
trend, the DX returns to batch overview mode.
• Using the FUNC Key
You can use the FUNC key for the following operations. For operating procedures,
see the reference for each respective operation. Entries marked with a * function the
same as in batch single mode.
Operation Name Description Reference
* Alarm ACK Executes alarm acknowledgement for all
activated alarms.
Section 3.8 in the User’s Manual.
* Alarm display reset Resets the alarm display. Section 3.12 in the User’s Manual.
* Media eject Puts the external memory into a state in
which it can be safely removed from the DX.
Operation Guide.
* Snapshot Saves the screen image data from the
active display to a CF card (in PNG format).
Section 6.6 in the User’s Manual.
* Manual sample Saves the instantaneous values of all
channels.
Section 6.5 in the User’s Manual.
* Save stop Aborts the manual data saving operation in
progress.
Section 4.8 in the User’s Manual.
Math start/stop Starts or stops computations on all
computation channels.
Section 3.2 in this manual.
Computation reset Resets computed results for all computation
channels.
Section 3.2 in this manual.
* Math ACK Clears the computation data dropout display. Section 9.4 in the User’s Manual.
* Edge switch Sets the event edge switch to on. Section 7.1 in the User’s Manual.
* Timer reset Resets the relative timer. Section 7.1 in the User’s Manual.
* Match timer reset Resets the single match time timer. Section 7.1 in the User’s Manual.
* Key lock Locks or unlocks keys. Section 8.1 in the User’s Manual.
* Logout Logs off from the DX. Section 8.3 in the User’s Manual.
* Locked ACK Executes the Locked ACK operation. Advanced Security Manual.
* Password change Changes the password used to log on to the
DX.
Section 8.3 in the User’s Manual.
Text field Displays the text field for the batch group
that you select.
Section 3.8 in this manual.
* Builder screen Displays the custom display’s builder
screen.
IM04L41B01-04E.
* Favorite registration Registers the current display as a favorite. Section 3.7 in this manual.
* Standard display Registers the current display as the
standard DX display.
Section 5.14 (DX1000)
Section 5.15 (DX2000)
in the User’s Manual
System info Displays the system information screen. Section 2.5 in the User’s Manual.
Network info Displays the network information screen. Section 2.5 in the User’s Manual.
* SNTP Synchronizes the DX’s time with an SNTP
server.
Section 1.8 in the Communication
Manual.
* E-Mail start/stop Starts or stops e-mail transmission. Section 1.4 in the Communication
Manual.
* E-Mail test Confirms sending of e-mail and the details
of the transmission.
Section 1.4 in the Communication
Manual.
* FTP test Checks the connection between the DX and
the FTP server.
Section 1.7 in the Communication
Manual.
3.4 Using Batch Overview Mode