12. MAINTENANCE
The product enters the operable status as soon as the power is
turned on, but requires 10 to 15 minutes of warm-up to meet
the performance requirements.
12.1 Calibration Apparatus
Calibrator (Yokogawa Meters & Instruments CA71 or
equivalent): 1
Setting tool for adjustment (Refer to 8.2 Connecting the
Setting Tools in this manual.)
12.2 Calibration Procedure
(1) Connect the instruments as shown in Fig.12.1 and Fig.
8.2.
(2) Produce the input signal equivalent to 0% of the input
range from the calibrator to the product. Then, read the
input value of Display items, A01: INPUT1 using the
VJ77 or JHT200 and check that the input value is within
the rated accuracy range. Take the same procedure for
the input signal equivalent to 25, 50, 75 and 100% of the
input range and check that the input values are within
the rated accuracy range.
For alarm output, check the relay action by the alarm in-
dicator lamp or resistance of output terminals.
If the input values are out of the rated accuracy range,
adjust the input signal level referring to the users
manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or for JHT200 Handy Terminal (IM JF81-
02E).
1011
3 2
1
4
56
789
11
10
8
9
7
5
2
1
3
3
4
GND
ALM2 (NO)
COM
ALM1 (NO)
COM
Calibrator
Calibrator
Calibrator
Input
With SINK current
Without SINK current
Alarm-2 output
Alarm-1 output
Power supply
L+
+
N
Calibrator
+
Fig. 12.1