Yokogawa EJX115A Bedienungsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 9
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
Supply unit
The supply unit must be certied by a Notied
body as FISCO model and following trapezoidal or
rectangular output characteristic is used.
Uo = 14...17.5 V (I.S. maximum value)
Io based on spark test result or other
assessment,
No specication of Lo and Co is required on the
certicate or label.
Cable
The cable used to interconnect the devices needs
to comply with the following parameters:
Loop resistance Rc: 15...150 Ω/km
Inductance per unit length Lc: 0.4...1 mH/km
Capacitance per unit length Cc: 45...200 nF/km
Length of spur cable: max. 60 m (IIC and IIB)
Length of trunk cable: max. 1 km (IIC) or 5 km
(IIB)
Terminators
The terminator must be certied by a Notied body
as FISCO model and at each end of the trunk
cable an approved line terminator with the following
parameters is suitable:
R = 90 . . . 102
C = 0 . . . 2.2 µF. (0.8...1.2 µF is required in
operation)
The resistor must be infallible according to IEC
60079-11.
Number of Devices
The number of devices (max. 32) possible on a
eldbus link depends on factors such as the power
consumption of each device, the type of cable used,
use of repeaters, etc.
Entity Model
Non-Hazardous
Locations
Hazardous Locations
F0206_R03.ai
Terminator
Ex i
Field Instruments
(Passive)
Hand-
held-
Terminal
Supply Unit and
Safety Barrier
Terminator
Data
U
U
I
I.S. eldbus system complying with Entity model
I.S. values Power supply-eld device:
Po Pi, Uo Ui, Io Ii
Calculation of max. allowed cable length:
Ccable Co ∑Ci ∑Ci (Terminator)
Lcable Lo ∑Li
Number of Devices
The number of devices (max. 32) possible on a
eldbus link depends on factors such as the power
consumption of each device, the type of cable used,
use of repeaters, etc.
c. ATEX Flameproof Type
Caution for ATEX ameproof type
Note 1. EJX series pressure transmitters with
optional code /KF21 for potentially
explosive atmospheres:
No. KEMA 07ATEX0109
Applicable Standard:
EN 60079-0:2006, EN 60079-1:2004,
EN 61241-0:2006, EN 61241-1:2004
Type of Protection and Marking Code:
Ex d IIC T6...T4, Ex tD A21 IP6x T85, T100,
T120
Group: II
Category: 2G, 2D
Enclosure: IP66 and IP67
Ambient Temperature for gas-proof:
–50 to 75°C (T6), –50 to 80°C (T5),
and –50 to 7C (T4)
Maximum Process Temperature (Tp.) for
gas-proof:
85°C (T6), 100°C (T5), and 120°C (T4)
Maximum Surface Temperature for dust-
proof:
T8C (Tamb.:40* to 40°C, Tp.: 85°C)
T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40* to 80°C, Tp.: 120°C)
* –1C when /HE is specied.
Note 2. Electrical Data
Supply voltage: 32 V dc max.
Output current: 15 mA dc
Note 3. Installation
All wiring shall comply with local installation
requirements.
The cable entry devices shall be of a certied
ameproof type, suitable for the conditions of
use.
Seitenansicht 4