Yokogawa 202 Field Mounting Rate Totalizer Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Computers Yokogawa 202 Field Mounting Rate Totalizer herunter. Yokogawa 202 Field Mounting Rate Totalizer User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - MODEL 202D

FIELD MOUNTEDRATE TOTALISERMODEL 202D1 February 1999

Seite 2

Specification62. SPECIFICATIONGeneralDisplay: LCD which is continuously powered.Resettable Total: 7 digits with 10mm (0.4") high digits. Resetta

Seite 3 - CONTENTS

Specification7DC Power/Alarm VersionOutputs: Two open collector outputs suitable for drivingDC solenoids or external relays. The outputs canbe progra

Seite 4

Operation83. OPERATIONThe Model 202D Rate Totaliser accepts a frequency or pulse input from a widerange of flowmeters. The instrument is fully progra

Seite 5 - 1. INTRODUCTION

Operation93.2 TEST MODEThe 202D has a Test Mode which can be entered by simultaneously pressing all 3front panel keys. The tests are as follows:Low

Seite 6

Operation103.3 FILTERINGFrequency fluctuations caused by pulsating flow through a flowmeter can interferewith the precision of the rate. For this re

Seite 7 - 1.1 MODEL NUMBER DESIGNATION

Operation11Filter Factor vs Time to Reach New Reading (for a step change in input signal) 0204060801001200 10 20 30 40 50 60 70 80 90 100Filter Factor

Seite 8

Operation123.4 CALCULATION OF RATE AND TOTALThe flow rate, R, is calculated as follows:where f is the input frequency in Hz (pulses/second).H is the

Seite 9

Operation133.5 TOTAL CONVERSIONThe Total Conversion Factor is programmed to enable the rate to be displayed inone engineering unit and the totals to

Seite 10 - 2. SPECIFICATION

Operation143.6 FREQUENCY CUTOFFA frequency cutoff can be programmed below which flow rate is not registered.Input frequencies at or below the cutoff

Seite 11

Programming154. PROGRAMMINGThe Model 202D is fully programmable with all parameters being stored in non-volatile memory.The Program Mode can be entere

Seite 13 - 3.2 TEST MODE

Programming164.1 PROGRAM STEPS Step CommentCAL 0 Pulse Output (applies to DC Power/Alarm version only).0 = No pulse output, low and high alarms.1 = S

Seite 14 - 3.3 FILTERING

Programming17 Step CommentCAL 6 Filter.The filter constant for filtering the input signal.1 No filtering.to99 Very heavy filtering.CAL 7 Decimal Point

Seite 15 - Operation

Programming18 Step CommentCAL 12 High Alarm or Pulse Output Factor - whole numbers.CAL 13 High Alarm or Pulse Output Factor - digits after the decimal

Seite 16

Example195. EXAMPLEA flowmeter produces 20.538 pulses per litre and has a maximum outputfrequency on 200Hz. It is required to display the flow rate i

Seite 17 - 3.5 TOTAL CONVERSION

Versions206. VERSIONSThe following table summarises the features of each of the different versions ofthe Model 202D:Model Number 202D.X0 202D.X3 202D.

Seite 18 - 3.6 FREQUENCY CUTOFF

Versions216.1 BATTERY POWERED VERSIONThe battery powered version of the Model 202D is designed for operation in thefield without external power sourc

Seite 19 - 4. PROGRAMMING

Versions226.2 DC POWER VERSIONThe DC power version will operate from an external power source between 9-28VDC and draws no more than 4mA. This enabl

Seite 20 - 4.1 PROGRAM STEPS

Versions23Specification for Alarm OutputsMaximum Current (sink): 200mA.Maximum Voltage: 30Vdc.Saturation Voltage: 0.8Vdc across outputs when in the &q

Seite 21

Versions246.3 RELAY AND 4-20mA OUTPUT VERSIONThis version combines features of the DC powered with a 4-20mA output.The 4-20mA output provides a two-w

Seite 22

Versions25Typical ConnectionConnection to a Sensor requiring External Power

Seite 23 - 5. EXAMPLE

CONTENTS1. Introduction 11.1 Model Number Designation 31.2 Intrinsic Safety Considerations 42. Specification 63. Operation 83.1 Display 83.2 Test Mod

Seite 24 - 6. VERSIONS

Flowmeter Input267. FLOWMETER INPUTThe Model 202D has an input conditioning circuit which will accept signals frommost pulse or frequency producing fl

Seite 26 - 6.2 DC POWER VERSION

Flowmeter Input281. Squarewave, CMOS or Pulse2. Open CollectorWith 15µA/150µA internal pull up current3. Reed Switch - Battery PoweredWith 15µA intern

Seite 27

Flowmeter Input294. Reed Switch - External DC PowerWith 150µA internal pull up currentNote: For a switch or reed input with contact bounce link DBH c

Seite 28

Flowmeter Input306. Namur Proximity SwitchNote: Use this connection for a DC powered version of the Model 202D.7. Namur Proximity Switch - External D

Seite 29 - Typical Connection

Intrinsic Safety Connections318. INTRINSIC SAFETY CONNECTIONSWhen installing the Model 202D in hazardous areas, the wiring and installationmust com

Seite 30 - 7. FLOWMETER INPUT

Intrinsic Safety Connections328.2 SIMPLE APPARATUSDevices such as reed switches which can be classed as "simple apparatus", asdefined in th

Seite 31 - Flowmeter Input

Intrinsic Safety Connections33

Seite 32 - 2. Open Collector

Intrinsic Safety Connections34

Seite 33 - 5. Coils

Intrinsic Safety Connections358.4 ALARM OUTPUTSThe low alarm and high alarm/pulse output can be connected to suitably certifieddevices providing the

Seite 34 - 6. Namur Proximity Switch

9. Installation 379.1 Wall Mounting 379.2 Panel Mount Version 389.3 Removing the Front Panel 399.4 The Main Electronics 419.5 Wiring 429.6 Terminal

Seite 35 - CONNECTIONS

Intrinsic Safety Connections36

Seite 36 - 8.3 NAMUR PROXIMITY SWITCHES

Installation379. INSTALLATION9.1 WALL MOUNTINGA wall mounting bracket is supplied with each instrument. Round head screwsshould be used to attach th

Seite 37 - Intrinsic Safety Connections

Installation389.2 PANEL MOUNT VERSIONThe panel mount version of the Model 202D is supplied with two panel mountbrackets and plug-in terminals which a

Seite 38

Installation399.3 REMOVING THE FRONT PANELThe front panel should be removed as follows:1. Remove the top and bottom cover strips (ie. the dark plasti

Seite 40

Installation419.4 THE MAIN ELECTRONICSThe front section of the housing contains the microprocessor and display. It ispossible to adjust the display

Seite 41 - 9. INSTALLATION

Installation429.5 WIRINGWhen connecting the 202D it is good practice to use shielded cable. The shieldshould be connected to earth at one end of the

Seite 42 - 9.2 PANEL MOUNT VERSION

Installation439.6 TERMINAL DESIGNATIONSAll versions8 Pulse (+) / Coil Input7 Pulse (-) / Coil Input6 High Alarm (+) or Pulse Output (+) if installed5

Seite 43 - 9.3 REMOVING THE FRONT PANEL

Index44Index4-20mA Output, 24AAccumulated Total, 8Alarm Outputs, 35BBattery Powered, 21CCAL Sequences, 15Cutoff Frequency, 16DDC Power, 22Decimal Poin

Seite 44 - Installation

Introduction11. INTRODUCTIONThe Model 202D Rate Totaliser is a microprocessor based instrument whichaccepts a frequency or pulse input from a wide ran

Seite 45 - 9.4 THE MAIN ELECTRONICS

Introduction2♦ Unlike the previous Model 202, the 202D has an additional mounting option -it is available in a PANEL MOUNT version.The Model 202D Rate

Seite 46 - 9.5 WIRING

Introduction31.1 MODEL NUMBER DESIGNATIONThe Model Number of the 202D describes the power & output options installedand the mounting options.Mode

Seite 47 - 9.6 TERMINAL DESIGNATIONS

Introduction41.2 INTRINSIC SAFETY CONSIDERATIONSThe Model 202D is certified for use in hazardous areas and has both CENELECand CSA NRTL/C approvals.T

Seite 48

Introduction5Relay OutputsThe outputs can be connected to IS circuits with the following maximumvalues:Ui = 28VIi = 93mAPi = 653mWThe internal capacit

Kommentare zu diesen Handbüchern

Keine Kommentare