User’sManualIM 04L65B01-01EN1st EditionModel GA10/GA10CL/GA10UPData Logging Software User’s Manual
Blank
1-1IM 04L65B01-01ENBefore Using the Product123456789101112AppIndexChapter 1 Before Using the Product1.1 OverviewData Logging Software GA10 is used t
1-2IM 04L65B01-01EN Chapter 1 Before Using the ProductData Collection ProjectGA10 collects data in units of projects. Projects are created by users to
1-3IM 04L65B01-01EN Chapter 1 Before Using the ProductFeatures to improve reliabilityGA10 features the following functions to ensure reliable data col
1-4IM 04L65B01-01ENChapter 1 Before Using the ProductConnectable Devices and SoftwareThe following table lists the devices and software applications t
1-5IM 04L65B01-01EN1.4 Menu and IconsThis section describes the GA10 menus and icons and page references on how to use them.Menu before logging in To
1-6IM 04L65B01-01ENMenu Description See pages...Tag Display From.Switch tag display format 4-2User Display Form.Switch user display format 4-2StyleSwi
2-1IM 04L65B01-01ENPreparation123456789101112AppIndexChapter 2 Preparation2.1 Preparation from Installation up to Data Collection and RecordingThe f
2-2IM 04L65B01-01ENAfter the installation is complete, start the client, and log in to the server.7 On the Start menu, click All Programs, SMARTDAC+
2-3IM 04L65B01-01EN2.3 Registering the Administrator PasswordAfter installation, first set the administrator (admin) password. The administrator can
2-4IM 04L65B01-01ENChapter 2 PreparationNoteUser names are case-sensitive. Differences between the administrator and users and changing and deleting
2-5IM 04L65B01-01ENChapter 2 Preparation 2.6 Other Operations If Necessary2.6.1 Starting (Restarting) and Stopping the Server To manually start o
2-6IM 04L65B01-01EN2 Scroll down to find DLGServer in the Name column. Check the Status column.The DLGServer status should be indicating Started, and
2-7IM 04L65B01-01EN2.6.3 Entering a License Number (GA10/GA10CL/GA10UP)When entering a license number, use Windows administrator privileges. If you
2-8IM 04L65B01-01EN2.6.4 UninstallationTo uninstall GA10, follow the procedure below.1 On the Start menu, click Control Panel and Programs and Featu
3-1IM 04L65B01-01ENConfiguring and Starting Data Collection and Recording123456789101112AppIndexChapter 3 Configuring and Starting Data Collection an
3-2IM 04L65B01-01ENNoteFor details on where the Ethernet port is located and the hierarchy of setting menus, see the user’s manual of the relevant dev
3-3IM 04L65B01-01EN3.2.4 Starting Data Collection and RecordingClick the icons that are displayed on the tab on the right side of the screen to colle
3-4IM 04L65B01-01ENNoteYou cannot perform the following operations while data is being collected.• Register devices from the Online Devices List to t
3-5IM 04L65B01-01EN• Export procedure1 From the list of projects, select the project that you want to export.Click to select.2 On the File menu, cl
iIM 04L65B01-01ENIntroductionThis manual explains how to use Data Logging Software GA10 (hereafter referred to as GA10). To ensure correct use, please
3-6IM 04L65B01-01ENRenaming a project To rename a project, follow the procedure below.1 From the list of projects, select the project that you want
3-7IM 04L65B01-01EN3.3.3 Registering Devices to ConnectAfter you create a project, register the devices to collect and record data from.The Device Se
3-8IM 04L65B01-01ENSearching for Network DevicesSearch for devices connected to the network to display them in the Online Devices List. Simply click t
3-9IM 04L65B01-01ENConnectable Devices and InterfacesNameInterface 1RS-232 RS-422RS-485Ethernet (connection port number)μR10000 Yes Yes Yes 34260μR200
3-10IM 04L65B01-01ENStarting the Web Application (GX/GP Only)Click Setting in the device information display area to start the Web application for co
3-11IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording 3.3.4 Setting TagsGA10 collects and records data from multipl
3-12IM 04L65B01-01ENTag SettingsTag settings are used to set display groups and other settings in a project. Therefore, even if you change the device
3-13IM 04L65B01-01ENCollectively Editing TagsTo collectively edit setup data, you must select the target setup data and then click a button on the act
3-14IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording3.3.5 Setting Display GroupsThe GA10 Monitor Page can display m
3-15IM 04L65B01-01ENWaveform SettingsWaveform settings are explained below.(1) No. These are waveform numbers assigned sequentially starting with W01
iiIM 04L65B01-01ENSoftware License AgreementIMPORTANT - PLEASE READ CAREFULLY BEFORE INSTALLING OR USING:THANK YOU VERY MUCH FOR SELECTING SOFTWARE
3-16IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and RecordingNote• When you assign tags automatically, the settings of all d
3-17IM 04L65B01-01EN3.3.6 Registering Data Collection Method and Monitor PageAfter setting the display groups, register the data collection method an
3-18IM 04L65B01-01ENSetting Data Collection Conditionsa Data timeTimestamps are attached to data that GA10 collects from devices. You can set the typ
3-19IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording The Monitor Sets can be arranged vertically or horizontally on
3-20IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording3.3.7 Setting the Data Recording MethodGA10 saves the data coll
3-21IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording The following settings are available on the Record Setting Pag
3-22IM 04L65B01-01ENRecording IntervalSelect the interval from the drop-down list.Options: 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 20 s, 30 s, 1
3-23IM 04L65B01-01EN• If the stop condition is set to LevelThe setting procedure is the same as described above.GA10 operates in the following manner
3-24IM 04L65B01-01EN3.3.8 Configuring Mail SettingsGA10 can send email when alarms occur or when the communication status changes.Configure email set
3-25IM 04L65B01-01ENThe available email transmission conditions are listed below.• Send an email when an alarm occurs.• Send an email when the commu
iiiIM 04L65B01-01EN5.3 If Yokogawa believes that a Claim may be made or threatened, Yokogawa may, at its option and its expense, either a) procure fo
3-26IM 04L65B01-01ENSMTP Server SettingsEnter the following items.• SMTP server name (up to 255 characters)• Port number (0 to 65535)• Resend Times
3-27IM 04L65B01-01ENBody of the Sent EmailThe body of email messages consists of the message specified by the user and the message automatically added
3-28IM 04L65B01-01EN3.3.9 Setting Project Access PrivilegesIn GA10, you can set access privileges at the project level separately from the server acc
3-29IM 04L65B01-01EN Chapter 3 Configuring and Starting Data Collection and Recording Access Privilege Types and Operation ScopeThe table below show
3-30IM 04L65B01-01ENNote• “All Users” apply to all users registered in the server. Therefore, note that if you assign access privileges to “All Users
3-31IM 04L65B01-01ENThe application name, topic name, and item number that are used to retrieve data with the DDE client are shown below.Item Text Str
3-32IM 04L65B01-01ENNote• Projects that you can simultaneously control are those that you have Operator or higher privileges for.• If a Modbus devic
3-33IM 04L65B01-01ENNode Structure of Modbus Device Definition FilesLevel 0 Level 1 Level 2 Level 3 Level 4 Level 5 Description QuantityModbusDevice D
3-34IM 04L65B01-01ENNode Name Attribute Type Type Mandatory Range Default ValueDescriptionAlarm\Type Kind enum enum “OFF”,“H”,“L”,“dH”,“dL”,“RH”,“RL”,
3-35IM 04L65B01-01ENModbus Device Definition File Example<?xml version="1.0" encoding="utf-8"?><ModbusDevice Type="S
ivIM 04L65B01-01ENUsing Open Source SoftwareHeimdalThe password-management function of the following product uses Heimdal source code for AES authenti
3-36IM 04L65B01-01EN <Value Register="ALM" Mask="0x0002"></Value> </Alarm> <Alarm>
3-37IM 04L65B01-01EN </Alarm> </Alarms> </Channel> <Channel Name="A/M1" DecimalPos="0" Min=
Blank
4-1IM 04L65B01-01ENMonitoring Data Collection123456789101112AppIndexChapter 4 Monitoring Data Collection4.1 Monitoring on the Monitor PageThis secti
4-2IM 04L65B01-01EN4.1.2 Displaying the Monitor PageOpen a project, and click the Monitor Page icon on the Project tab to open the Monitor Page.In Si
4-3IM 04L65B01-01EN4.2 Monitoring on the Trend Display4.2.1 Displayed ContentScan intervalGroup tabWaveformGridTrip lineAlarm display Time axisY-axi
4-4IM 04L65B01-01ENChapter 4 Monitoring Data Collection • Y-axis Display Zone You can switch the Y-axis display zone. section 4.2.3• Waveform L
4-5IM 04L65B01-01ENChapter 4 Monitoring Data Collection 4.2.4 Showing and Hiding Waveforms (Using the Legend)The legend can be displayed in tag dis
4-6IM 04L65B01-01EN• Data No. A sequence number of collected data points taking the first collected data point to be zero.• Alarm indicator The st
4-7IM 04L65B01-01EN4.3 Monitoring on the Digital Display4.3.1 Displayed ContentAlarm indicatorTag display areaTag colorTag nameMeasurement bar displ
vIM 04L65B01-01EN123456789101112AppIndexContentsIntroduction ...
4-8IM 04L65B01-01EN4.5 Monitoring AlarmsAn alarm Monitor Set displays alarm information of monitored tags in three formats.4.5.1 Group OverviewClick
4-9IM 04L65B01-01EN• Alarm Type IconsDisplayed ContentDescriptionHigh limit alarm, measurement high limit alarm, deviation high limit alarm, setting
4-10IM 04L65B01-01EN• Alarm ACK Operation and Alarm Indication Transition The following figure shows how the alarm indication transitions as an alar
4-11IM 04L65B01-01EN• Device Communication Status The status of communication with the devices in the Device List is displayed. Nothing is displayed
4-12IM 04L65B01-01EN4.9 Things to Consider4.9.1 Time Zone and Daylight Saving TimeBe sure to set the same time zone and daylight saving time setting
4-13IM 04L65B01-01EN4.10 Viewing the LogYou can view the log that the server sends in the Log dialog box. You can open the Log dialog box at any time
5-1IM 04L65B01-01ENManaging Recording Data123456789101112AppIndexChapter 5 Managing Recording Data5.1 Displaying a List of Data FilesClick the Data
5-2IM 04L65B01-01EN• Sorting the File List Click a column title to sort the file list on the basis of the clicked column. Click it again to sort in
6-1IM 04L65B01-01ENManaging Users123456789101112AppIndexChapter 6 Managing Users6.1 Administrator and UsersIn GA10, you can set server access privil
viIM 04L65B01-01ENChapter 4 Monitoring Data Collection4.1 Monitoring on the Monitor Page ...
6-2IM 04L65B01-01EN6.3 Changing User InformationThis section explains how to change the user full name and password. This procedure can also be perfo
6-3IM 04L65B01-01EN6.4 Registering and Deleting UsersOnly the administrator can register and delete other users.6.4.1 Registering a New Users1 Star
6-4IM 04L65B01-01ENChange Project’ s Owner dialog box4 From the New Owner list, select a user.Any user registered in the server can become a project
6-5IM 04L65B01-01EN3 To proceed, click OK.The dialog box closes, and the name of the user who locked the project disappears from the project.4 Selec
Blank
7-1IM 04L65B01-01ENTroubleshooting123456789101112AppIndexChapter 7 Troubleshooting7.1 Messages That GA10 May DisplayMessages may appear on the scree
7-2IM 04L65B01-01EN Chapter 7 Troubleshooting Code Message Description and SolutionE3004 Unable to connect to the server. Check for problems in the c
7-3IM 04L65B01-01ENChapter 7 Troubleshooting Code Message Description and SolutionE3040 Operation failed because Project is deleted. The project may
7-4IM 04L65B01-01EN7.2 Frequently Asked Questions (FAQ)Q1 Can the server and client be installed and run in the same PC?A1Yes. The server and client
7-5IM 04L65B01-01ENWhen the communication interference is eliminated, the backfill function operates automatically. The restored data is saved as a ne
viiIM 04L65B01-01ENChapter 7 Troubleshooting7.1 Messages That GA10 May Display ...
7-6IM 04L65B01-01ENQ6 A communication error occurred between the client and server. Will data collection continue?A6Because data collection is perfo
7-7IM 04L65B01-01ENQ9 The device data and the data collected and recorded by the software are not synchronized. Why?A9Data collected using Device ti
7-8IM 04L65B01-01ENWhat is PC time?PC time is the time information that the server PC uses. In PC time mode, the server attaches PC timestamps on the
7-9IM 04L65B01-01EN• Monitor The trend monitor displays data based on a single time axis. If there are multiple devices, the Monitor Set will be div
Blank
Kommentare zu diesen Handbüchern